7<br />

Electrical connections<br />

EV terminal (external switching contact)<br />

This terminal can be used for example for the safety switch<br />

of floor heating. This protects the floor heating against too<br />

high boiler water temperatures (external manual reset high<br />

limit). The boiler is shut down when the external switching<br />

contact is opened.<br />

The normally closed contacts of a LWCO will shut down<br />

burner operation but allow the pump to continue to operate<br />

in case of a low water condition.<br />

DWV<br />

Terminal for connection of an external 3-way valve (not<br />

used).<br />

PK<br />

Connector for the primary loop pump 120V 60Hz.<br />

PS<br />

Connector for the DHW tank pump 120V 60Hz.<br />

PZ<br />

Connector for the DHW recirculating pump 120V 60Hz.<br />

Netz<br />

Main power connector 120V 60Hz (-15% +10%).<br />

120-volt connections<br />

CAUTION<br />

Make sure that the power consumption of each<br />

of the terminals 7 – 9 (see circuit diagram) does<br />

not exceed 250 W or 5 Amp.<br />

28<br />

Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!