6<br />

Installation<br />

6.5 Combustion Air and Ventilation<br />

Openings<br />

Provisions for combustion and ventilation air must be made<br />

in accordance with section 5.3, Air for Combustion and<br />

Ventilation, of the National Flue Gas Code, ANSI Z223.1, or<br />

Sections 7.2, 7.3 or 7.4 of CAN/CGA B149, Installation<br />

Codes, or applicable provisions of the local building codes.<br />

CAUTION:<br />

BOILER DAMAGE AND OPERATIONAL<br />

FAILURES !<br />

Due to insufficient or lacking openings for<br />

combustion air and/or ventilation of the boiler<br />

room.<br />

Provisions for combustion air and ventilation are<br />

always required, regardless whether the<br />

combustion air is taken from the outside (sealed<br />

combustion) or inside (non sealed combustion<br />

for combustion).<br />

Insufficient ventilation of the boiler room can<br />

lead to high air temperatures. This can result in<br />

boiler damage.<br />

– Make sure that intake and exhaust openings<br />

are sufficiently sized and no reduction or<br />

closure of openings takes place.<br />

– When the problem is not resolved, do not<br />

operate the boiler.<br />

– Please note these restrictions and its<br />

dangers to the operator of the boiler.<br />

WARNING:<br />

BOILER DAMAGE !<br />

due to contaminated air.<br />

– Boiler must be clear and free from<br />

combustible materials, gasoline and other<br />

flammable vapors and liquids, and corrosive<br />

liquids and vapors.<br />

Never use chlorine and hydrocarbon<br />

containing chemicals (such as spray<br />

chemicals, solution and cleaning agents,<br />

paints, glues etc) in the vicinity of the boiler.<br />

– Do not store and use these chemicals in the<br />

boiler room.<br />

– Avoid excessive dust formation and build-up.<br />

NOTICE<br />

When one expects contaminated combustion<br />

air (near swimming pools, chemical cleaning<br />

operations and hair salons), sealed combustion<br />

operation is recommended.<br />