Installation<br />

Do not exceed the total equivalent venting length of 100 feet<br />

(30,480 mm) (GB142-24/30/45) and 60 feet (18,288 mm)<br />

(GB142-60) maximum requirement each for the intake and<br />

exhaust piping.<br />

See table 4 for the Friction Loss Equivalent in piping and<br />

fittings.<br />

Example:<br />

When you end up using 3 x 45°-elbows and the concentric<br />

vent kit, then the total venting length may not exceed 88 feet<br />

(26.84 m) (GB142-24/30/45) or 48 feet (14.65 m)<br />

(GB142-60).<br />

3 x 45°-elbow = 3 x 3 ft (0.91 m) = 9 ft (2.73 m)<br />

concentric vent kit = 3 ft (0.91 m)<br />

Fittings or Piping<br />

Equivalent<br />

feet<br />

m<br />

45 degree elbow 3 0.91<br />

90 degree elbow 5 1.52<br />

plastic pipe per foot 1 0.30<br />

concentric vent kit 3 0.91<br />

Table 4 Friction Loss Equivalent in piping and fittings<br />

Total friction loss equivalent = 12 ft (3.64 m)<br />

Total venting length for this example is:<br />

GB142-24/30/45 = 100 ft (30.48 m) - 12 ft (3.64 m) =<br />

88 feet (26.84 m)<br />

GB142-60 = 60 ft (18.29 m) - 12 ft (3.64 m) =<br />

48 feet (14.65 m).<br />

NOTICE<br />

The minimum covering wall thickness is<br />

1" (25 mm).<br />

The maximum covering wall thickness is<br />

16" (406 mm).<br />

CAUTION !<br />

Vent connectors serving appliances vented by<br />

natural draft shall not be connected into any<br />

portion of mechanical draft systems operating<br />

under positive pressure.<br />

NOTICE<br />

For Direct venting properly reassemble and<br />

reseal the vent and air-intake systems.<br />

6.8 Conversion to Propane<br />

To convert the boiler to propane , following the instructions<br />

in the " Propane, Conversion Kit" Instruction manual.<br />

Available kits see page 59 "spare parts, pos. 43".<br />