BC10 basic controller<br />
9.2 Carrying out additional tasks<br />
9.2.1 Carrying out a flue gas test<br />
The "Chimney Sweep" d button is used for the flue gas<br />
test.<br />
The heating control system works at the maximum flow<br />
temperature for 30 minutes. This is set on the BC10 basic<br />
controller using the "maximum heater temperature" knob.<br />
During flue gas testing the decimal point lights up in the<br />
display.<br />
• Press and hold the "Chimney Sweep" d button<br />
(< 5 seconds) until the decimal point is displayed.<br />
• Carry out the flue gas test.<br />
• Press the "Chimney Sweep" d button to interrupt the<br />
flue gas test.<br />
9.2.2 Selecting partial load operation (e. g. during flue<br />
gas testing)<br />
You can operate the boiler at a reduced boiler capacity<br />
during flue gas testing. This reduction is only effective for the<br />
duration of the flue gas test.<br />
• Press the "Chimney Sweep" d button (max. 2 seconds)<br />
until the decimal point shows in the status display. This<br />
will switch on the flue gas test.<br />
• Press and hold the "Chimney Sweep" d and "Service"<br />
e buttons (for approx. 5 seconds) to enter the partial<br />
load mode.<br />
• Press the "Reset" c button to reduce the boiler capacity<br />
percentage.<br />
+<br />
Example: boiler capacity reduced to 50 % of the rated boiler<br />
capacity.<br />
• Press the "Chimney Sweep" d button to increase the<br />
boiler capacity percentage.<br />
L50.<br />
• When test is completed, press the "Service" e button<br />
until the temperature indication is displayed.<br />
• Press the "Chimney Sweep" d button until the decimal<br />
point is cleared from the display.<br />
9.2.3 Switching the heating system to manual mode<br />
In manual mode the heating system can be operated independently<br />
of an external control unit. The boiler is operated<br />
with the heating system temperature set on the right knob<br />
serving as the target value.<br />
A blinking decimal point is displayed while manual mode is<br />
active.<br />
• Press the "Chimney Sweep" d button (for more than<br />
5 seconds) until the decimal point in the status display<br />
flashes.<br />