9<br />

BC10 basic controller<br />

Resetting the boiler or resetting faults<br />

If the boiler is down due to a fault, you can reset the boiler<br />

by pressing the "Reset" c button. This is only possible for<br />

so-called lock-out faults. There is another type of fault, socalled<br />

blocking faults, that reset themselves when the cause<br />

has been remedied.<br />

• Press the "Reset" c button to reset the boiler.<br />

The display shows "rE" while resetting.<br />

It is only possible to reset the boiler when a lock-out code<br />

(blinking fault code) is visible in the display.<br />

rE<br />

NOTICE<br />

If the burner returns to fault mode after resetting<br />

the boiler, you must resolve the fault using the<br />

servicing section in this document.<br />

Contact your supplier if necessary.<br />

9.1.3 Displaying the heating system status and/or<br />

faults<br />

The display of the BC10 basic controller shows the status of<br />

the heating system.<br />

In the event of a fault the display immediately shows the fault<br />

or the warning in the form of an error code (see<br />

subsection 13.2). The status display will flash if the fault is a<br />

lock-out fault.<br />

• Press the "Service" e button to switch between status<br />

displays or to read out the service and error codes.<br />

• Resolve the fault see subsection 13.3.<br />

The following status displays can be seen depending on the<br />

operating conditions:<br />

Displays<br />

(examples)<br />

Values Meaning Operating condition/Remedy<br />

140<br />

P12<br />

H 7<br />

1)<br />

P21<br />

-H<br />

1)<br />

(changing)<br />

-H<br />

140<br />

P12<br />

number 0 ... 199 2)<br />

Current boiler water temperature (in °F)<br />

> P15 Current system pressure (in psi) Normal operating conditions<br />

P3 ... P12<br />

number 0 ... 199 2)<br />

P3 ... P12<br />

Warning:<br />

System pressure is too low (between 3 and 12 psi<br />

= 0.2 and 0.8 bar)<br />

Current boiler water temperature (in °F)<br />

Current system pressure (in psi)<br />

Warning<br />

Heating system remains operational<br />

between 12 psi and 3 psi (0.8 and 0.2 bar).<br />

Fill the heating system and restore the<br />

minimum filling pressure ( 14.5 psi =<br />

1.0 bar).<br />

The system pressure is shown for<br />

10 minutes after which the standard<br />

display returns.<br />

Table 8<br />

Possible status displays<br />

1) Standard display for this operating condition. This display appears after 5 minutes if no button is pressed.<br />

2)<br />

The temperature is higher as 199° when 199 is blinking in the display.<br />

40<br />

Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!