Casestudie Breakdown prediction Contell PILOT - Transumo
Casestudie Breakdown prediction Contell PILOT - Transumo
Casestudie Breakdown prediction Contell PILOT - Transumo
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
This mode forces the system to store a measuring point every single minute instead<br />
of every 15 minutes. 15<br />
Column number five shows the last measured value. Depending on the classified<br />
current state of the attached device this value can be up to 15 minutes old within<br />
normal operation mode. To be able to classify such temperature values, critical limits<br />
are set, as described in section 2.3. These limits can be seen in column number<br />
seven and eight for every single device.<br />
Figure 3-3: XiltriX - The Main Screen [DEMO06]<br />
In Addition to these limits, a delay time can be defined for minimum and maximum<br />
temperature alarms in column six and nine. After having passed a critical<br />
temperature limit, the system is waiting for a predefined time, before it alarms the<br />
person in charge. The last two columns contain date, time and the most critical<br />
temperature value of a current alarm. Entries within these two columns can only be<br />
cleared by an alarm reset. 16<br />
15 See section 3.2.1 for details<br />
16 See section 3.2.2 for details<br />
24