Chapter 3 Wiring Methods and Materials
Chapter 3 Wiring Methods and Materials
Chapter 3 Wiring Methods and Materials
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
ARTICLE 310 -<br />
CONDUCTORS FOR GENERAL WIRING<br />
310.60<br />
n\ .5<br />
. \tJ.,.,<br />
" .<br />
.' ,<br />
.....<br />
~<br />
E<br />
- E<br />
'I . ,u 0<br />
~<br />
Detail 1<br />
0><br />
290 mm x 290 mm ~<br />
(11.5 in. x 11.5 in.) 190 mm (7.5 in.)<br />
Electrical duct bank<br />
Detail 2<br />
One electrical duct<br />
475 mm x 475 mm<br />
(19 in. x 19 in.)<br />
190 mm (7.5 in.)<br />
Electrical duct bank<br />
Three electrical ducts Detail 3<br />
or<br />
475 mm x 675 mm<br />
(19 in. x 27 in.)<br />
, ,<br />
'<br />
Electrical duct bank<br />
. v • 'I Six electrical ducts<br />
~ or<br />
190 mm 190 mm<br />
(7.5 in.) (7.5 in.) .5<br />
It)<br />
675 mm x 290 mm<br />
(27 in. x 11.5 in.)<br />
Electrical duct bank<br />
Three electrical ducts<br />
t:::.<br />
E<br />
E<br />
o<br />
0><br />
~<br />
190 mm 190 mm<br />
(7.5 in.) (7.5 in.)<br />
675 mm x 475 mm<br />
(27 in. x 19 in.)<br />
Electrical duct bank<br />
Six electrical ducts<br />
r<br />
600mm<br />
600mm<br />
(24 in.) (24 in.) ~<br />
.<br />
• 1 I. •• .'.<br />
DetailS Detail 6 Detail7 Detail 8<br />
Buried 3 Buried 3 Buried triplexed Buried triplexed<br />
conductor conductor cables (1 circuit) cables (2 circuits)<br />
cable<br />
cables<br />
190<br />
rn<br />
mm 190 mm 190 mm 190 mm 190 mm<br />
(7.5 in.) (7.5 in.) (7.5 in.) (7.5 in.) 600mm<br />
(7.5 in.)<br />
(24 in.)<br />
Detail 9<br />
Detail 10<br />
Buried single-conductor<br />
Buried single-conductor<br />
cables (1 circuit)<br />
cables (2 circuits)<br />
Legend<br />
Note: Minimum burial depths to top electrical ducts or cables shall be<br />
in accordance with 300.50. Maximum depth to the top of electrical<br />
duct banks shall be 750 mm (30 in.) <strong>and</strong> maximum depth to the top<br />
of direct buried cables shall be 900 mm (36 in,).<br />
G:] Backfill (earth or concrete)<br />
o Electrical duct<br />
• Cable or cables<br />
Figure 310.60 Cable Installation Dimensions for Use with Table 310.77 Through Table 310.86.<br />
2008 Edition NATIONAL ELECTRICAL CODE 70-155