378.30 ARTICLE 382 - NONMETALLIC EXTENSIONS<br />

378.30 Securing <strong>and</strong> Supporting. Nonmetallic wireway<br />

shall be supported in accordance with 378.30(A) <strong>and</strong> (B).<br />

(A) Horizontal Support. Nonmetallic wireways shall be<br />

supported where run horizontally at intervals not to exceed<br />

900 mm (3 ft), <strong>and</strong> at each end or joint, unless listed for<br />

other support intervals. In no case shall the distance between<br />

supports exceed 3 m (10 ft).<br />

(D) Vertical Support. Vertical runs of nonmetallic wireway<br />

shall be securely supported at intervals not exceeding<br />

1.2 m (4 ft), unless listed for other support intervals, <strong>and</strong><br />

shall not have more than one joint between supports. Adjoining<br />

nonmetallic wireway sections shall be securely fastened<br />

together to provide a rigid joint.<br />

378.44 Expansion Fittings. Expansion fittings for nonmetallic<br />

wireway shall be provided to compensate for thermal<br />

expansion <strong>and</strong> contraction where the length change is expected<br />

to be 6 mm (0.25 in.) or greater in a straight run.<br />

FPN: See Table 352.44 for expansion characteristics of<br />

PVC conduit. The expansion characteristics of PVC nonmetallic<br />

wireway are identical.<br />

378.56 Splices <strong>and</strong> Taps. Splices <strong>and</strong> taps shall be permitted<br />

within a nonmetallic wireway, provided they are accessible.<br />

The conductors, including splices <strong>and</strong> taps, shall not<br />

fill the nonmetallic wireway to more than 75 percent of its<br />

area at that point.<br />

378.58 Dead Ends. Dead ends of nonmetallic wireway<br />

shall be closed using listed fittings.<br />

378.60 Grounding. Where equipment grounding is required,<br />

a separate equipment grounding conductor shall be<br />

installed in the nonmetallk wireway. A separate equipment<br />

grounding conductor shall not be required where the<br />

grounded conductor is used to ground equipment as permitted<br />

in 250.142.<br />

378.70 Extensions from Nonmetallic Wireways. Extensions<br />

from nonmetallic wireway shall be made with cord<br />

pendants or any wiring method of <strong>Chapter</strong> 3. A separate<br />

equipment grounding conductor shall be installed in, or an<br />

equipment grounding connection shall be made to, any of<br />

the wiring methods used for the extension.<br />

380.1 Scope. This article covers the use <strong>and</strong> installation<br />

requirements for multioutlet assemblies.<br />

380.2 Use.<br />

(A) Permitted. The use of a multioutlet assembly shall be<br />

permitted in dry locations.<br />

(D) Not Permitted. A multioutlet assembly shall not be<br />

installed as follows:<br />

(1) Where concealed, except that it shall be permissible to<br />

surround the back <strong>and</strong> sides of a metal multioutlet assembly<br />

by the building finish or recess a nonmetallic<br />

multioutlet assembly in a baseboard<br />

(2) Where subject to severe physical damage<br />

(3) Where the voltage is 300 volts or more between conductors<br />

unless the assembly is of metal having a thickness<br />

of not less than 1.02 mm (0.040 in.)<br />

(4) Where subject to corrosive vapors<br />

(5) In hoistways<br />

(6) In any hazardous (classified) location, except as permitted<br />

b,!.~r:~.~!~iUl~lil;:Col,~<br />

380.3 Metal Multioutlet Assembly Through Dry Partitions.<br />

It shall be permissible to extend a metal multioutlet<br />

assembly through (not run within) dry partitions if arrangements<br />

are made for removing the cap or cover on all exposed<br />

portions <strong>and</strong> no outlet is located within the partitions.<br />

I. General<br />

382.1 Scope. This article covers the use, installation, <strong>and</strong><br />

construction specifications for nonmetallic extensions.<br />

382.2 Definitions.<br />

III. Construction Specifications<br />

378.120 Marking. Nonmetallic wireways shall be marked<br />

so that the manufacturer's name or trademark <strong>and</strong> interior<br />

cross-sectional area in square inches shall be visible after<br />

installation. Marking for limited smoke shall be permitted<br />

on the nonmetallic wireways that have limited smokeproducing<br />

characteristics.<br />