16.11.2014 Views

Chapter 3 Wiring Methods and Materials

Chapter 3 Wiring Methods and Materials

Chapter 3 Wiring Methods and Materials

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

ARTICLE 312 -<br />

CABINETS, CUTOUT BOXES, AND METER SOCKET ENCLOSURES<br />

312.10<br />

Table 312.6(A) Minimum Wire-Bending Space at Terminals <strong>and</strong> Minimum Width of <strong>Wiring</strong> Gutters<br />

Wires per Terminal<br />

1 2 3 4 5<br />

Wire Size (AWG or<br />

kcrnil) mrn in. mrn in. mrn in. mm in. mrn in.<br />

14-10 Not specified<br />

8-6 38.1 1 1 /2<br />

4-3 50.8 2<br />

2 63.5 2'/2<br />

1 76.2 3<br />

110-2/0 88.9 3 1 /2 127 5 178 7<br />

3/0-4/0 102 4 152 6 203 8<br />

250 114 4 1 /2 152 6 203 8 254 10<br />

300-350 127 5 203 8 254 10 305 12<br />

400-500 152 6 203 8 254 10 305 12 356 14<br />

600-700 203 8 254 10 305 12 356 14 406 16<br />

750-900 203 8 305 12 356 14 406 16 457 18<br />

1000-1250 254 10<br />

1500-2000 305 12<br />

Note: Bending space at terminals shall be measured in a straight line from the end of the lug or wire connector (in the direction that the wire leaves<br />

the terminal) to the wall, bamer, or obstruction.<br />

enter or leave the enclosure through the wall opposite its<br />

terminal.<br />

(2) Conductors Entering or Leaving Opposite Wall.<br />

Table 312.6(B) shall apply where the conductor does<br />

enter or leave the enclosure through the wall opposite its<br />

terminal.<br />

Exception No.1: Where the distance between the wall <strong>and</strong><br />

its terminal is in accordance with Table 312.6(A), a conductor<br />

shall be permitted to enter or leave an enclosure<br />

through the wall opposite its terminal, provided the conductor<br />

enters or leaves the enclosure where the gutter joins<br />

an adjacent gutter that has a width that conforms to Table<br />

312.6(B) for the conductor.<br />

Exception No.2: A conductor not larger than 350 kcmil<br />

shall be permitted to enter or leave an enclosure containing<br />

only a meter socket(s) through the wall opposite its terminal,<br />

provided the distance between the terminal <strong>and</strong> the<br />

opposite wall is not less than that specified in Table<br />

312.6(A) <strong>and</strong> the terminal is a lay-in type, where the terminal<br />

is either of the following:<br />

(a) Directed toward the opening in the enclosure <strong>and</strong><br />

within a 45 degree angle of directly facing the enclosure<br />

wall<br />

(b) Directly facing the enclosure wall <strong>and</strong> offset not<br />

greater than 50 percent of the bending space specified in<br />

Table 312.6(A)<br />

FPN: Offset is the distance measured along the enclosure<br />

wall from the axis of the centerline of the terminal to a line<br />

passing through the center of the opening in the enclosure.<br />

(C) Conductors 4 AWG or Larger. Installation shall comply<br />

with 300.4(G).<br />

312.7 Space in Enclosures. Cabinets <strong>and</strong> cutout boxes<br />

shall have sufficient space to accommodate all conductors<br />

installed in them without crowding.<br />

312.8 Enclosures for Switches or Overcurrent Devices.<br />

Enclosures for switches or overcurrent devices shall not be<br />

used as junction boxes, auxiliary gutters, or raceways for conductors<br />

feeding through or tapping off to other switches or<br />

overcurrent devices, unless adequate space for this purpose is<br />

provided. The conductors shall not fill the wiring space at any<br />

cross section to more than 40 percent of the cross-sectional<br />

area of the space, <strong>and</strong> the conductors, splices, <strong>and</strong> taps shall<br />

not fill the wiring space at any cross section to more than<br />

75 percent of the cross-sectional area of that space.<br />

312.9 Side or Back <strong>Wiring</strong> Spaces or Gutters. Cabinets<br />

<strong>and</strong> cutout boxes shall be provided with back-wiring<br />

spaces, gutters, or wiring compartments as required by<br />

312.11(C) <strong>and</strong> (D).<br />

II. Construction Specifications<br />

312.10 Material. Cabinets, cutout boxes, <strong>and</strong> meter socket<br />

enclosures shall comply with 312.1O(A) through (C).<br />

(A) Metal Cabinets <strong>and</strong> Cutout Boxes. Metal enclosures<br />

within the scope of this article shall be protected both inside<br />

<strong>and</strong> outside against corrosion.<br />

FPN: For information on protection against corrosion, see<br />

300.6.<br />

(B) Strength. The design <strong>and</strong> construction of enclosures<br />

within the scope of this article shall be such as to secure<br />

2008 Edition NATIONAL ELECTRICAL CODE<br />

70-165

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!