<strong>Vigilohm</strong>: presentation<br />
<strong>Vigilohm</strong> <strong>System</strong>:<br />
choosing a communication interface<br />
the power of a<br />
communicating system<br />
The power of the <strong>Vigilohm</strong> <strong>System</strong> lies in the<br />
capacity it offers for communication between<br />
all its devices, thereby ensuring insulation<br />
monitoring and complementary functions<br />
such as automatic locating of faults or the<br />
anticipation of their occurrence.<br />
In addition, the <strong>Vigilohm</strong> <strong>System</strong> is capable<br />
of communicating with a supervisor or a<br />
PLC, i.e. it can both transmit data to and<br />
receive data from such units.<br />
The transfer of information takes place:<br />
c via the internal <strong>Vigilohm</strong> <strong>System</strong> bus for<br />
communication between the devices;<br />
c via the external JBUS for communication<br />
with a supervisor or PLC.<br />
In both cases, the use of an internal or<br />
external bus requires a communication<br />
interface.<br />
four interfaces<br />
The <strong>Vigilohm</strong> <strong>System</strong> offers four interfaces:<br />
c the XLI200 interface, for the transmission<br />
of information from the insulation monitoring<br />
device and XD308C detectors to a<br />
supervisor or PLC via JBUS. In this way,<br />
a PC can access information concerning<br />
the presence of faults and the identification<br />
of the faulty circuit. This interface cannot be<br />
used with XL308/316 or XML308/316<br />
devices and connects only to the XM300C<br />
and XD308C (the XLI200 cannot be used<br />
with XML monitoring-locating devices or with<br />
XL locating devices).<br />
c the XLI300 interface, for the transmission<br />
of measurements and measurement<br />
parameters from the XM300C and XD308C<br />
devices to a supervisor. This interface is<br />
used on single busbar installations. The<br />
exclusion of other insulation monitoring<br />
devices found on the same installation is<br />
managed automatically;<br />
c the XTU300 interface, for communication<br />
between the <strong>Vigilohm</strong> <strong>System</strong> and a<br />
supervisor, like the XLI300 interface. This<br />
interface is required for installations with<br />
multiple busbars and bus coupler circuit<br />
breakers. It manages the exclusion of other<br />
insulation monitoring devices found on the<br />
same installation and the link between the<br />
locators and their corresponding insulation<br />
monitoring devices;<br />
c the XAS interface, indispensable for the<br />
operation of the communication bus in the<br />
absence of one of the three other interfaces.<br />
interface selection table<br />
IMD associated only one XML308/316 IMD with at least IMD with a least<br />
with XD308C device 1 locator 1 locator<br />
communicating + 1 set of busbars + several sets<br />
detectors, whatever the<br />
of busbars with<br />
installation configuration<br />
bus coupling<br />
without supervision ---- ---- XAS XTU300<br />
with supervision XLI200 XLI300 XLI300 XTU300<br />
E20791<br />
E20792<br />
MV/LV<br />
XML308<br />
One set of busbars without supervisor<br />
XM300c<br />
MV/LV<br />
XAS<br />
XL308<br />
supervisor<br />
or<br />
PLC<br />
DB100957 E20790A<br />
MV/LV<br />
XML308<br />
One set of busbars with supervisor<br />
XM300c<br />
MV/LV<br />
supervisor<br />
or<br />
PLC<br />
XLI300<br />
XL308<br />
supervisor<br />
or<br />
PLC<br />
MV/LV<br />
MV/LV<br />
MT/BT<br />
MT/BT<br />
XML308<br />
XM300c<br />
XTU300<br />
XM300C<br />
XM300C<br />
XLI200<br />
XD308C<br />
XL308<br />
XD308C<br />
Several sets of busbars with bus coupling and with or without supervisor<br />
14<br />
application of the measurement voltage<br />
internal <strong>Vigilohm</strong> <strong>System</strong> bus<br />
JBUS bus