<strong>Vigilohm</strong>: functions and characteristics<br />

communicating <strong>Vigilohm</strong> <strong>System</strong><br />

XLI200, XLI300, XTU300 and XAS communication interfaces<br />

use<br />

When two or more communicating devices<br />

(XM300C, XML308/316, XL308/316 or<br />

XD308C) are used or when communication<br />

with a supervisor is required, it is necessary<br />

to connect one (and only one) interface to<br />

the communication bus.<br />

If no XTU300 or XLI300 interface is<br />

included, operation of the <strong>Vigilohm</strong> <strong>System</strong><br />

bus will require an XAS interface.<br />

functions<br />

The interface allows communication<br />

between the <strong>Vigilohm</strong> <strong>System</strong> and a<br />

supervisor or PLC using a JBUS type<br />

protocol (except X25).<br />

It transmits the information provided by the<br />

<strong>Vigilohm</strong> <strong>System</strong>:<br />

c prevention and fault alarms from XM300C<br />

or XML308/316 monitoring devices (only<br />

XM300C for XLI200);<br />

c fault alarms from XML308/316 or<br />

XM308/316 locators (except XLI200);<br />

c insulation resistance and capacitance<br />

measurements;<br />

c threshold settings;<br />

c fault alarms and faulty circuit identification<br />

from XD308C detectors.<br />

The interface also allows the thresholds to<br />

be set form the supervisor.<br />

device XLI200 XLI300 XTU300 XAS<br />

function<br />

interface between the <strong>Vigilohm</strong> <strong>System</strong> bus and a supervisor or PLC c c c<br />

power supply to <strong>Vigilohm</strong> <strong>System</strong> bus c c c c<br />

operates with monitoring device XM300C c c c c<br />

mon.-loc. device XML308/316 c c c<br />

locator XL308/316 c c c<br />

detector<br />

XD301/312<br />

XD308C c c c c<br />

maximum configuration monitoring device XM300C and/or XML308/316 4 (1) 4 4 4<br />

locator XL308/316 8 8<br />

detector XD308C 16 8 8 8<br />

electrical characteristics<br />

auxiliary supply voltage 50/60 Hz 220/240 V AC 115/127 V AC 115/127 V AC 115/127 V AC<br />

380/415 V AC 220/240 V AC 220/240 V AC 220/240 V AC<br />

380/415 V AC 380/415 V AC 380/415 V AC<br />

500/525 V AC 500/525 V AC 500/525 V AC<br />

consumption 30 VA c c c c<br />

dielectric strength 2500 V c c c c<br />

mechanical characteristics<br />

weight gross 2.228 kg 2.228 kg 2.228 kg<br />

net 1.864 kg 1.864 kg 1.864 kg<br />

metal case with insulated front c c c c<br />

degree of protection<br />

IP30<br />

degree of protection of front<br />

IP40<br />

other characteristics<br />

interfacing possible with supervisor c c c<br />

JBUS connector Sub D 9-pin (not supplied) c c c<br />

communication with other devices via 4-wire data bus c c c c<br />

temperature range storage - 25 °C to + 70 °C<br />

operation - 5 °C to + 55 °C<br />

installation<br />

vertical mounting on front plate c c c c<br />

connection<br />

<strong>Vigilohm</strong> <strong>System</strong> bus 1.5 mm 2 tunnel terminals c c c c<br />

external bus RS485 sub D9 female connector c c c<br />

communication<br />

speed (bauds) adjustable 300... 19200 300... 19200 300... 19200<br />

per fault 9600 9600 9600<br />

data length (bits) 8 8 8<br />

parity none none none<br />

start bits 1 1 1<br />

stop bits 1 1 1<br />

(1) only XM300C.<br />