<strong>Vigilohm</strong>: presentation<br />
insulation monitoring and associated functions<br />
continuity of supply<br />
Continuity of supply is a need that must<br />
always be satisfied by electrical installations,<br />
along with the protection of life and property.<br />
The IT system provides the best guarantee<br />
in terms of continuity of supply. Even when a<br />
first insulation fault is present, the installation<br />
can continue to supply power without<br />
endangering human life. The first fault must<br />
however be detected and repaired before a<br />
second fault occurs.<br />
IO316_123<br />
principle<br />
Insulation monitoring is provided on IT<br />
systems to detect and indicate insulation<br />
faults as soon as they occur.<br />
The basic function is carried out by an<br />
Insulation Monitoring Device (IMD), also<br />
referred to in certain documentation as a<br />
permanent or continuous insulation monitor<br />
(PIM or CIM respectively). The monitoring<br />
device injects a DC or low-frequency<br />
AC voltage between the installation and<br />
earth. The insulation resistance is determined<br />
from the resulting current. This technique can<br />
be used on all types of installations: AC, DC,<br />
rectified, mixed AC/DC, etc.<br />
DB100664<br />
measuring, indicating and<br />
locating insulation faults<br />
<strong>Vigilohm</strong> <strong>System</strong>, with or without a<br />
communication bus, fulfils the following<br />
basic functions:<br />
c measurement of insulation level on all<br />
types of installations<br />
c manual or automatic locating of insulation<br />
faults.<br />
<strong>Vigilohm</strong> <strong>System</strong> with a<br />
communication bus<br />
The communication bus adds the following<br />
possibilities:<br />
c measurement of the insulation resistance<br />
and earth leakage capacitance of each<br />
circuit<br />
c centralisation of fault locating<br />
measurements on the IMD display units<br />
c communication with a supervisor<br />
(transmission of measurements and<br />
reception of settings).<br />
6