E19502<br />

MERLIN GERIN<br />

XML316<br />

1 2 3 4 5 6 7 8<br />

9 10 11 12 13 14 15 16<br />

9 8 10 1 7 2 3 6 4 5<br />

1. display indicating measurements<br />

concerning the overall installation or each<br />

monitored circuit, and information<br />

concerning the device settings;<br />

2. red self-test light, indicating device faults.<br />

3. light indicating that a transient fault has<br />

occurred.<br />

4. 5 lights indicating the insulation level.<br />

5. instruction manual stored in a drawer on<br />

the front face<br />

6. sealable cover ensuring tamperproof<br />

settings.<br />

7. function keys for:<br />

c accessing earth coupling capacitance<br />

readings;<br />

c setting thresholds;<br />

c accessing three last values of transient<br />

insulation faults;<br />

c reading measurements made on individual<br />

circuits by the internal locator;<br />

c remote access to faults detected by XL308<br />

or XL316 detectors;<br />

c choice of language.<br />

8. two indicator lights continuously display<br />

the insulation level of the overall installation.<br />

9. 8 or 16 indicating lights indicate faulty<br />

circuits.<br />

10. light indicating that a transient fault has<br />

occurred.<br />

test<br />

i<br />

auxiliaries<br />

Cardew surge limiter: page 43.<br />

ZX limiting impedance to create an<br />

impedance-earthed neutral: page 44.<br />

PHT1000 subassembly if the device is to be<br />

used on 1000-1700 V installations: page 44.<br />

type of installation to be monitored<br />

AC or mixed<br />

phase-to phase voltage<br />

AC/DC IT systems with XML308/316 connected to neutral < 760 or 1700 V AC (1)<br />

with XML308/316 connected to phase < 440 or 1000 V AC (1)<br />

frequency<br />

45-400 Hz<br />

size of installation<br />

0 to 30 km of cable<br />

DC or rectified line voltage < 500 or 1200 V DC (1)<br />

IT systems<br />

electrical characteristics<br />

ohmmeter<br />

digital<br />

range for insulation resistance readings<br />

0.1 to 999 kΩ<br />

signalling for overall instal. number of thresholds 2 (sealable settings)<br />

for each circuit number of thresholds 1 (sealable settings)<br />

threshold settings for overall instal. 1st threshold (preven.) 1 to 299 kΩ<br />

instal. and circuits 2nd threshold (fault) 0.2 to 99.9 kΩ<br />

number of toroids that can be connected XML308 8<br />

(1 per channel) XML316 16<br />

polling time<br />

15 s. per channel<br />

dielectric strength<br />

2500 V<br />

auxiliary supply voltage 50/60 Hz 115/127 V AC<br />

220/240 V AC<br />

380/415 V AC<br />

500/525 V AC<br />

auxiliary supply voltage tolerances -15 % to +10 %<br />

maximum device consumption<br />

30 VA<br />

measurement voltage<br />

6 V<br />

measurement current<br />

5 mA max.<br />

50 Hz/DC impedance 22 kΩ<br />

device test<br />

self-test and manual test<br />

failsafe feature (2)<br />

as standard<br />

changeover output contact quantity 3 (1 failsafe)<br />

breaking capacity of AC 400 V p.f. = 0.7 3 A<br />

output contacts 230 V p.f. = 0.7 5 A<br />

DC 220 V L/R = 1 ms 0.45 A<br />

120 V L/R = 1 ms 0.65 A<br />

48 V L/R = 1 ms 2.5 A<br />

24 V L/R = 1 ms 10 A<br />

circuit breaker position indication contacts (3) : voltage supplied 24 V<br />

(voltage and current supplied by XAS, max. current supplied 10 mA (short-circuit)<br />

CLI or XTU interfaces)<br />

connection cross-sections rigid conductors 1 to 1.5 mm 2<br />

flexible conductors 0.75 to 1.5 mm 2<br />

mechanical characteristics<br />

weight<br />

sheet-metal case (horizontal mounting)<br />

restrictions for use<br />

The XML308/316 operates by injecting lowfrequency<br />

signals (2.5 Hz). It should not be<br />

used for circuits that include variable speed<br />

drives if this equipment continuously<br />

generates a signal with a similar frequency<br />

(≤ 5 Hz).<br />

4.5 kg<br />

disconnectable screw terminal block<br />

degree of protection flush mounting IP 30<br />

other characteristics<br />

types of toroid to be used<br />

A, OA (XS compatible)<br />

interfacing possible with<br />

supervisor<br />

multi-language display<br />

English/French<br />

tamperproof settings<br />

protected by access code or sealable cover<br />

temperature range operating - 5 °C to + 55 °C<br />

storage - 20 °C to + 70 °C<br />

(1) The upper limit is extended to the second value by adding a PHT1000 subassembly.<br />

(2) Failsafe feature: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault.<br />

(3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its operating status.<br />