Specifications<br />

SPECIFICATIONS<br />

Following are specifications for the <strong>iSTAR</strong> <strong>Pro</strong> <strong>4U</strong> <strong>Rack</strong> <strong>Mount</strong>:<br />

TABLE 3. Physical Specifications<br />

Physical<br />

Dimensions (H x W x D)<br />

Space Requirements<br />

Environmental<br />

Weight<br />

Misc. Alarms<br />

Temperature Alarm<br />

18 x 48 x 74 cm<br />

(7 x 19 x 29 in)<br />

<strong>4U</strong> (standard rack units)<br />

0° to 50° C (32° to 122° F),<br />

5 to 95% relative humidity, non-condensing<br />

34 kg (74 lbs)<br />

Fan failure, High temperature<br />

60° +/- 6°C, (140° +/- 10°F)<br />

TABLE 4. Electrical Specifications<br />

Electrical<br />

Power Requirements<br />

Power (Typical/Max/Min)<br />

Heat Dissipation (Typical)<br />

AC Input Circuit Breaker Rating<br />

UPS Operation<br />

Memory and RTC Backup<br />

Max Lock Power (Total Output)<br />

115 VAC, 60 Hz<br />

75W/300W/50W<br />

500 BTU/h<br />

5A<br />

Battery charging included, with optional<br />

17Ah batteries (5) provides nominal four hours<br />

backup time; 48 hour recharge time<br />

On-board rechargeable NimH batteries provide<br />

minimum 12 hours retention of RAM and RTC (Real<br />

Time Clock)<br />

16A<br />

Individual Lock Current Limit 2.5A<br />

Lock Relay Ratings<br />

250,000 cycles<br />

8