TWINDOSE <strong>35</strong> – System for dishwashers<br />
3.2.4 Potentiometer POT4 (OFA TIME)<br />
1s.<br />
Disabled<br />
255 sec<br />
The OFA alarm is activated when the detergent concentration in the tank does not reach the set point within the<br />
time set using the POT4 (OFA TIME) potentiometer.<br />
As soon as detergent dosage begins, TWINDOSE <strong>35</strong> doses in conductometric mode (with probe) for the OFA time<br />
set using the POT4 (OFA TIME) potentiometer. Once this period of time has expired, if the detergent pump is still<br />
running the system goes into an OFA1 alarm phase:<br />
• The alarm LED flashes.<br />
• The buzzer sounds intermittently.<br />
• During this initial phase the pumps do not cut out.<br />
This alarm status ends if the detergent pump stops before the second OFA time (OFA2) has expired.<br />
If the detergent pump continues dosing for a further OFA interval, the device enters a second OFA phase, known<br />
as OFA2.<br />
During this alarm phase (OFA2):<br />
• The buzzer sounds continuously.<br />
• The LED stays lit permanently.<br />
• The detergent pump stops.<br />
PLEASE NOTE: The detergent pump will not start up again. To reset proper functioning, eliminate the<br />
cause of the alarm and then switch the system off and on again.<br />
The OFA time can be set using the POT4 (OFA TIME) trimmer, for a period of between 1 second and 255<br />
seconds.<br />
To disable the OFA alarm, turn the POT4 (OFA TIME) trimmer all the way to the left.<br />
3.2.5 Potentiometer POT5 (DETER INIT CHARGE)<br />
1sec<br />
255 sec<br />
This potentiometer manages the dosing time for the detergent pump during the first charging phase, and it is<br />
activated when TWINDOSE <strong>35</strong> receives a signal on the CHARGE SIGNAL terminal.<br />
The time setting can vary between 1 and 255 seconds.<br />
TWINDOSE <strong>35</strong> code 0000136655 rev. 1.0 18