26<br />

5.3 Mounting the pump station<br />

5.3.1 Notes on positioning and mounting the pump station<br />

Please observe the following notes on positioning and mounting:<br />

– Place the pump station in a way that:<br />

– the distance to the humidifier unit is as short as possible.<br />

Note: High-pressure hoses of 2 m, 5 m or 10 m length are available from stock.<br />

– it is freely accessible and there is enough space for convenient operation and maintenance<br />

(min. free space around pump station: laterally 0.5 m, in front 0.6 m).<br />

– The pump station is designed for the operation in protected rooms and must therefore not be<br />

installed outside.<br />

– Do not install the pump station in exposed locations or locations with heavy dust load.<br />

– The pump station must be installed only in a location having a water drain on the floor. If this<br />

is not possible, it is mandatory to provide water sensors to safely interrupt water supply in case<br />

of leakage. Furthermore, choose a suitable location that prevents damage to material assets in<br />

case of leakage.<br />

– The pump station is designed for installation on a load-carrying floor or on the optional floor<br />

stand. The pump station or the floor stand must be fixed with screws to the floor (protection<br />

against shifting and tilting).<br />

Caution! Do not install the pump station to vibrating components.