System c omponents<br />
With or without PRC470<br />
The modular <strong>EDS470</strong> system offers the possibility to realize an economical<br />
insulation fault location with minimum equipment. This minimum equipment<br />
consists of<br />
• insulation monitoring device of the IRDH265-4/365-4 or IR475LY series<br />
(possibly already available)<br />
• insulation fault test device PGH471<br />
• insulation fault evaluator <strong>EDS470</strong>-12<br />
• respective number of measuring current transformers<br />
Such a system can be used in simple interference-free IT systems without<br />
complex components.<br />
In operation without the PRC470 and without a serial connection to the PGH471,<br />
the <strong>EDS470</strong>-12 scans all the connected transformers in a rhythm of 25 seconds,<br />
even though the PGH471 insulation fault test device is not running. In this case,<br />
faults (I∆ > 10 A or interferences) can also be signalled.<br />
However, if significant interferences occur in the system, and <strong>EDS470</strong> system<br />
with PRC470 must be used in any case.<br />
Typical causes of interferences are e.g. converters with low-frequency leakage<br />
currents or switchgears and controls which produce transient leakage currents.<br />
For further information see chapter LIMITS OF INSULATION FAULT LOCATION.<br />
Apart from the control functions and the extended scanning possibilities, the<br />
PRC470 allows for adapting the <strong>EDS470</strong> system to different system parameters. In<br />
addition, it makes the entire <strong>EDS470</strong> system more comfortable and easier to use.<br />
It is generally possible to retrofit an existing <strong>EDS470</strong> system without PRC470 with<br />
a PRC470, if this becomes necessary due to modifications in the system.<br />
Already during planning, the considerations and the decision for an <strong>EDS470</strong><br />
system with or without PRC must be made. In case of doubt, an <strong>EDS470</strong> system<br />
with PRC470 must always be preferred. Ask for technical help from <strong>Bender</strong> if<br />
there are uncertainties.<br />
If one or more of the following points apply, it is necessary to use a PRC470:<br />
• IT systems with interferences caused by frequency converters, PLCs,<br />
clocked control.<br />
• Requirement for central scanning of all connected insulation fault<br />
evaluators.<br />
• Requirement for central control of all connected insulation fault evaluators<br />
and test devices.<br />
• Setting of different types of measuring current transformers.<br />
• Limitation of the current transformer scanning for each insulation fault<br />
evaluator.<br />
• Display of the test current for each measuring current transformer.<br />
• Targeted scanning of one measuring current transformer.<br />
• Serial connection to PCs by means of RS485 interface.<br />
• Requirement for central test functions.<br />