System c omponents<br />

With or without PRC470<br />

The modular <strong>EDS470</strong> system offers the possibility to realize an economical<br />

insulation fault location with minimum equipment. This minimum equipment<br />

consists of<br />

• insulation monitoring device of the IRDH265-4/365-4 or IR475LY series<br />

(possibly already available)<br />

• insulation fault test device PGH471<br />

• insulation fault evaluator <strong>EDS470</strong>-12<br />

• respective number of measuring current transformers<br />

Such a system can be used in simple interference-free IT systems without<br />

complex components.<br />

In operation without the PRC470 and without a serial connection to the PGH471,<br />

the <strong>EDS470</strong>-12 scans all the connected transformers in a rhythm of 25 seconds,<br />

even though the PGH471 insulation fault test device is not running. In this case,<br />

faults (I∆ > 10 A or interferences) can also be signalled.<br />

However, if significant interferences occur in the system, and <strong>EDS470</strong> system<br />

with PRC470 must be used in any case.<br />

Typical causes of interferences are e.g. converters with low-frequency leakage<br />

currents or switchgears and controls which produce transient leakage currents.<br />

For further information see chapter LIMITS OF INSULATION FAULT LOCATION.<br />

Apart from the control functions and the extended scanning possibilities, the<br />

PRC470 allows for adapting the <strong>EDS470</strong> system to different system parameters. In<br />

addition, it makes the entire <strong>EDS470</strong> system more comfortable and easier to use.<br />

It is generally possible to retrofit an existing <strong>EDS470</strong> system without PRC470 with<br />

a PRC470, if this becomes necessary due to modifications in the system.<br />

Already during planning, the considerations and the decision for an <strong>EDS470</strong><br />

system with or without PRC must be made. In case of doubt, an <strong>EDS470</strong> system<br />

with PRC470 must always be preferred. Ask for technical help from <strong>Bender</strong> if<br />

there are uncertainties.<br />

If one or more of the following points apply, it is necessary to use a PRC470:<br />

• IT systems with interferences caused by frequency converters, PLCs,<br />

clocked control.<br />

• Requirement for central scanning of all connected insulation fault<br />

evaluators.<br />

• Requirement for central control of all connected insulation fault evaluators<br />

and test devices.<br />

• Setting of different types of measuring current transformers.<br />

• Limitation of the current transformer scanning for each insulation fault<br />

evaluator.<br />

• Display of the test current for each measuring current transformer.<br />

• Targeted scanning of one measuring current transformer.<br />

• Serial connection to PCs by means of RS485 interface.<br />

• Requirement for central test functions.<br />

14<br />

TGH 1243E/02.2000