09.02.2015 Views

EDS470 - Bender

EDS470 - Bender

EDS470 - Bender

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

System c omponents<br />

<strong>EDS470</strong>-12<br />

The <strong>EDS470</strong>-12 is controlled by means<br />

of a microcontroller. Together with the<br />

measuring current transformers it is<br />

used to evaluate the test current signals<br />

generated by the PGH471. Up to 12<br />

measuring current transformers can be<br />

connected.<br />

In a given time pattern which is<br />

synchronized with the test cycle of the<br />

PGH471, the device subsequently<br />

A1 A2 K1 K2 K3 K4 K5 K6 K7 K8 K9<br />

I∆s<br />

<strong>EDS470</strong> K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12<br />

MONITOR<br />

ON<br />

ALARM<br />

FAULT<br />

1<br />

0<br />

SLAVE ADDRESS<br />

A4 A3 A2 A1 A0<br />

SLAVE<br />

RS485<br />

TEST<br />

RESET<br />

R/- MASTER<br />

A B R1 R2 l K12 K11 K10 11 12 14<br />

evaluates the signals from all measuring current transformers. If the fault current<br />

detected by a measuring current transformer exceeds the response value, the<br />

respective alarm LED of the LED chain and the alarm LED light up and the alarm<br />

relay switches. The alarm relay outputs a collective message for all measuring<br />

channels.<br />

When operating without an interface connection, the memory behaviour is set at<br />

the <strong>EDS470</strong>-12 itself. When operating with the control and indicating device<br />

PRC470, the memory behaviour is set via the PRC470.<br />

If fault memory is activated, the fault message of a channel remains stored until<br />

the RESET key is pressed or System-Reset at the PRC470 is activated.<br />

Some settings can only be carried out by means of the control and indicating<br />

device PRC470. These settings are:<br />

• split-core measuring current transformer<br />

• change of memory behaviour<br />

• change of N/O operation N/C operation<br />

• PEAK<br />

• number of the connected measuring current transformer.<br />

A system-reset and the reset of all alarm messages also can only be carried out<br />

via a PRC470.<br />

k1<br />

kn<br />

l<br />

a<br />

X<br />

Connection l of the measuring current transformer must be wired in a star<br />

connection to the common terminal block X (e.g. via a terminal block X).<br />

The maximum cable length (a) of the common l-connection to the terminal<br />

block X is:<br />

25 cm for a wire cross section of 2.5 mm 2<br />

15 cm for a wire cross section of 1.5 mm 2<br />

Note: the l-terminal must not be connected to the PE.<br />

18<br />

TGH 1243E/02.2000

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!