The insulation fault system is started by a potential-free NO contact on the<br />
insulation monitoring device. The following functions are possible in this case,<br />
depending on the particular connection:<br />
• Connection of the NO contact (21/24) to terminals GND an IN1 :<br />
the insulation fault location runs as long as the contact is closed. After<br />
every pass of the system, there is a pause of 5 minutes during which the<br />
insulation monitoring device can record new measurement values.<br />
Alarm relay<br />
Insulation Monitoring Device<br />
11<br />
21<br />
GND<br />
1 run 1 run<br />
PGH471<br />
12<br />
14<br />
22 24<br />
IN1<br />
pause 5 min<br />
• Connection of the potential-free NO contact to terminals GND and IN2 :<br />
The insulation fault location is started for one pass after which it is<br />
stopped. To be able to start the EDS system again, the input must be<br />
closed for approximately 6 seconds.<br />
• Connection of the NO contact (21/22) to terminals GND and IN3 :<br />
Suppression of the test cycle. No test cycle is emitted. This function is<br />
required if the insulation fault location system is monitoring several IT<br />
systems, and is being controlled centrally by one PRC470. In this case, a<br />
test cycle can only be emitted by the PGH471 insulation fault test device<br />
in the IT system where the insulation fault has occurred.<br />
Note: this kind of connection only makes sense in coupled IT systems.<br />
DIP switch PGH471<br />
SLAVE ADDRESS + 110<br />
25mA A3 A2 A1 A0 SLAVE<br />
1<br />
0<br />
10mA<br />
MASTER<br />
Setting of the max.<br />
test current (25 mA<br />
resp. 10 mA)<br />
Setting of MASTER or<br />
SLAVE mode<br />
Address setting in SLAVE<br />
mode<br />
Note: black = switch position<br />