7 Settings and adjustmen ts<br />

Factory settings<br />

All devices are delivered with the following factory settings:<br />

Insulation monitoring device:<br />

Factory settings depend on the type of device. Refer to the data sheet of the<br />

respective insulation monitoring device.<br />

Insulation fault test device PGH471:<br />

Operating mode of the alarm relay: N/O operation<br />

Address: 111<br />

Operating mode:<br />

SLAVE<br />

Max. test current:<br />

25 mA<br />

Insulation fault evaluator <strong>EDS470</strong>-12:<br />

Operating mode of the alarm relay: N/O operation<br />

Operating mode:<br />

SLAVE (with PRC470 or PGH471)<br />

Fault memory:<br />

ON<br />

Transformer type:<br />

Standard transformers W1-P … W4-P,<br />

W0-S … W5S, WR<br />

Address: 001<br />

Peak: n = 1<br />

Coupling device AGE470:<br />

No settings required<br />

Control and indicating device PRC470:<br />

Operating mode of the alarm relay: N/O operation<br />

Fault memory:<br />

ON (from Firmware Version 1.6 up)<br />

Address: 100<br />

Operating mode:<br />

MASTER<br />

Peak: n = 1<br />

Transformer type:<br />

Standard current transformer W1-P …<br />

W4-P, W0-S … W5S, WR<br />

Information concerning<br />

the insulation monitoring<br />

device<br />

The following are to be considered when choosing the insulation monitoring<br />

device.<br />

1) The internal DC resistance R i<br />

must be at least 120 kΩ.<br />

Devices with lower internal resistances must be disconnected from the system<br />

during insulation fault location.<br />

2) Device with two adjustable response values.<br />

In this case, response value 1 can for example be set to the value recommended<br />

in DIN VDE 0100 (100 Ω/V) or even more sensitive. This will then be<br />

considered as pre-warning.<br />

Response value 2 must start the EDS system. It should be set to a practicable<br />

and useful value which depends on the nominal voltage of the system.<br />

The setting of a practicable response value depends on some system<br />

parameters. The curves on the following pages can be used for determining this<br />

value.<br />

50<br />

TGH 1243E/02.2000