System c omponents<br />
AGE470<br />
By means of the coupling device AGE470, the range of nominal voltage of the<br />
<strong>EDS470</strong> system can be extended to AC 790 V resp. DC 960 V. About the<br />
connection refer to examples of complete circuits.<br />
AGE470<br />
R<br />
E<br />
Serial interface RS485<br />
The communication between several evaluators <strong>EDS470</strong>-12 and with the control<br />
and indicating device PRC470 as well as the test device PGH471 is carried out by<br />
means of a standardized serial interface RS485. The interface is a two-wire<br />
connection (device terminals A and B).<br />
The specification of the interface RS485 restricts the maximum cable length of the<br />
bus to 1200 m. For longer cables, additional measures (installation of repeaters,<br />
see chapter SYSTEM EXTENSIONS) are necessary. Cables longer than 1200 m<br />
should only be conceived after consulting BENDER.<br />
If interface cables are realized as subcircuits, the maximum cable length is<br />
restricted to 1 m. Longer subcircuit cables must be tested taking into<br />
consideration the conditions of the respective installation. The safe<br />
communication cannot be guaranteed for longer subcircuit cables.<br />
Terminating serial<br />
interfaces<br />
The serial connection must be terminated at both ends with a resistor of 120 Ω<br />
(0.4 W) (see picture). For each PRC470 and each PGH471 are 2 resistors<br />
included. Attention: single feeders are not terminated.<br />
1. device ... device last device<br />
A B A B A B<br />
120Ω<br />
single feeder max. 1 m<br />
120Ω<br />
maximum length of the RS485 bus: 1200 m<br />
TGH 1243E/02.2000<br />
22