Installation and wir ing<br />
Installing the measuring<br />
current transformers<br />
PE N L1 L2 L3 PE N L1 L2 L3<br />
Various methods of passing cables through<br />
the measuring current transformers.<br />
L+ L-<br />
L1 L2 L3<br />
When laying the wires or cables<br />
through the measuring current<br />
transformer, aim for the greatest<br />
possible balance in the centre of the<br />
current transformer and a rectangular<br />
routing for the conductors.<br />
Magnetic alternating fields such as those caused by AC consumers, can influence<br />
the sensitivity of the measuring current transformers. Therefore do not install<br />
devices which produce magnetic fields close to equipment such as transformers,<br />
throttles, or neighbouring conductors with high currents.<br />
Note: always choose the measuring current transformer with the smallest<br />
possible diameter. This will reduce the danger of influences from interference.<br />
9<br />
4,8<br />
24<br />
42<br />
55<br />
Schrauben M5<br />
Screws ø 5mm<br />
E<br />
W2-P and W3-P<br />
13<br />
7<br />
35<br />
70<br />
89<br />
122<br />
W4-P<br />
Fixing of measuring current transformers<br />
of the W1-S….W5-S… series.<br />
Fixing of measuring current transformers<br />
of the W1-P… W4-P series.<br />
TGH 1243E/02.2000<br />
38