1 General<br />

One determining factor for the availability of an electrical installation is the<br />

insulation resistance. It is first on the list of items to be considered with regard to<br />

electrical safety. This applies generally and regardless of the type of distribution<br />

system.<br />

Planning the installation of a safe, reliable power supply aiming the highest<br />

availability means:<br />

• Set-up of the power supply as IT system. In comparison with a<br />

distribution system with intentional earth connection of the active<br />

conductors, an improved operating reliability, improved fire protection,<br />

improved accident prevention as well as a higher permissible earth<br />

resistance are thereby achieved.<br />

• Use of the suitable insulation monitoring device. The advantages named<br />

in the previous paragraph stand or fall by the selection of the appropriate<br />

A-ISOMETER for the respective application. The advantages of the IT<br />

system cannot be used without a reliable monitoring system. A desired<br />

high level of the insulation resistance cannot be maintained in the long<br />

term without continuous monitoring.<br />

• Reduction of maintenance costs and downtimes thanks to the installation<br />

of an insulation fault location system. The quick localisation of an<br />

insulation fault immediately after it occurred is a long-cherished wish of<br />

the maintenance personnel. Without interruption and possible night and<br />

weekend work, the fault is located and indicated. The actual repair work<br />

can be carried out at an appropriate time.<br />

For the reliability of the power supply, it is decisive to maintain the good state of<br />

insulation. This is only possible by means of suitable monitoring devices. These<br />

devices cannot prevent insulation faults or the deterioration of the insulation.<br />

However, maintenance is considerably simplified by an early and quick<br />

detection with indication of the fault location.<br />

In the past, fault location often was time-consuming and complicated.<br />

Frequently, weekend work was necessary to localise the fault with the<br />

installation shut down.<br />

The modern <strong>EDS470</strong> insulation fault location system resolves these problems.<br />

Thanks to the automatic localisation of the insulation fault, the necessary repair<br />

becomes very simple, the required high insulation level is maintained. Fault<br />

localisation is carried out during operation, it is not necessary to shut down the<br />

system.<br />

For setting up a power supply as IT system, the relevant regulations (IEC364-4-<br />

41, DIN VDE 0100 T. 410) require that as soon as the first insulation fault occurs,<br />

it must be eliminated as quickly as possible. These requirements can be met by<br />

means of the insulation fault location system <strong>EDS470</strong>. Thus, the risk of an<br />

interruption of the power supply due to a possible second fault is significantly<br />

reduced.<br />

<strong>EDS470</strong> is an open modular system. For this reason, it can at an optimum be<br />

adapted to the individual conditions of the system. Later extensions are very<br />

simple and require only few devices and set-up work.<br />