Modular PLC – XC100/XC200<br />
4/118<br />
Technical Data<br />
Communication modules<br />
XIOC-…, XIOC-NET-…<br />
Interfaces<br />
Interfaces PROFIBUS DP, RS 485, EN<br />
50170<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
XIOC-NET-DP-M XIOC-NET-DP-S XIOC-NET-SK-M XIOC-SER<br />
PROFIBUS DP, RS 485, EN<br />
50170<br />
http://catalog.moeller.net<br />
RS485 RS232(C), RS422, RS485<br />
Protocol PROFIBUS-DP master (class 1) PROFIBUS-DP slave Suconet K, K1 Tranparent mode, Modbus<br />
master/dSlave, SUCOM A,<br />
Suconet-K slave<br />
Character formats 8E1, 8O1, 8N1, 8N2, 7E2,<br />
7O2, 7N2, 7E1<br />
<strong>Control</strong> and signal cables RTS, CTS, DTR, DSR, DCD<br />
Data transfer rate kBit/s 9.6 to 12000 9.6 to 12000 187.5, 375 0.3 …57.6<br />
187.5, 375 (Suconet)<br />
Potential isolation Yes Yes Yes Yes (RS485, RS422)<br />
Number of slaves 124 16<br />
Transmit/receive data 3500 Byte each Max. 244 Byte 250 bytes per COM 250 Byte per slave<br />
120 Byte per slave<br />
(Suconet-K slave)<br />
Bus terminating resistors Switchable Switchable Switchable Switchable for RS485,<br />
RS422<br />
Plug arrangement 9-pole SUB-D socket<br />
connector<br />
9-pole Sub-D socket Plug-in terminal block RS232: 9 pole SUB-D plug<br />
RS485, 422: plug terminal<br />
block<br />
Current consumption mA 300 300 275 275<br />
Weight kg 0.2 0.2 0.2 0.2<br />
Number of modules XC100: 1<br />
XC200:3<br />
XC100: 1<br />
XC200: 3<br />
XC100: 2<br />
XC200: 4<br />
XC100: 2<br />
XC200: 4<br />
Slots 1, 2, 3 1, 2, 3 As required As required<br />