Modular PLC PS416<br />
4/146<br />
Technical Data<br />
Digital output cards<br />
PS416-OUT…<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
Digital output card PS416-OUT-400 PS416-OUT-410<br />
http://catalog.moeller.net<br />
General<br />
Standards EN 61131-2, EN 50178 EN 61131-2, EN 50178<br />
Ambient temperature °C 0…55 0…55<br />
Ambient temperature, storage °C –25…70 –25…70<br />
Weight kg 0.15 0.15<br />
Space requirement 4 space units = 1 slot 4 space units = 1 slot<br />
Electromagnetic compatibility (EMC) a Page 4/143 a Page 4/143<br />
Humidity class RH 1 RH 1<br />
Card power supply V DC 5 internal through bus 5 internal through bus<br />
External output voltage supply V DC 24 24<br />
Tolerance +20 %/-15 % +20 %/-15 %<br />
Residual ripple % F 5 F 5<br />
Protection against polarity reversal Yes Yes<br />
Current consumption<br />
Logic 5 V bus mA Normally 150 Normally 85<br />
External 24 V (no-load) mA Normally 230 Normally 70<br />
Power loss<br />
Logic 5 V bus W Approx. 0.74 Approx. 0.425<br />
External 24 V W Approx. 5.6 Approx. 4.5<br />
Outputs<br />
Number 16 8<br />
Rated current<br />
per output at Ue = 24 V Ie A 0.5 2<br />
Isolation between output and 5 V logic bus Yes Yes<br />
Terminals Plug-in screw terminal Plug-in screw terminal<br />
Terminal capacity mm 2 1.5 1.5<br />
Indication elements LED LED<br />
Short-circuit trip With manual reset<br />
Short-circuit trip, control mode 1 With manual reset<br />
Short-circuit trip, control mode 2 With automatic reset<br />
Parallel connection of outputs per card (per group) Max. 4 No<br />
Indication of monitoring activity<br />
LED Yes Yes<br />
ZAA Low active Low active<br />
Residual current on “Off” signal mA 300 400<br />
Signal range at Ue<br />
“Off” signal V 2.5 2<br />
"On" signal = rated voltage = rated voltage<br />
Rated current<br />
per output at Ue = 24 V Ie A 0.5 2<br />
per output at Umax Ie A 0.6 2.4<br />
Delay time<br />
On 0 V r 24 V ms 60 60<br />
Off 24 V r 0 V ms 100 700<br />
Utilization factor g % 1 1<br />
Duty factor % DF 100 100<br />
Monitoring<br />
Short-circuit Yes Yes, with manual reset<br />
Thermal Yes<br />
Overload Yes<br />
Operating frequency at inductive load To DC-13 To DC-13<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616