Modular PLC PS416<br />

4/146<br />

Technical Data<br />

Digital output cards<br />

PS416-OUT…<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

Digital output card PS416-OUT-400 PS416-OUT-410<br />

http://catalog.moeller.net<br />

General<br />

Standards EN 61131-2, EN 50178 EN 61131-2, EN 50178<br />

Ambient temperature °C 0…55 0…55<br />

Ambient temperature, storage °C –25…70 –25…70<br />

Weight kg 0.15 0.15<br />

Space requirement 4 space units = 1 slot 4 space units = 1 slot<br />

Electromagnetic compatibility (EMC) a Page 4/143 a Page 4/143<br />

Humidity class RH 1 RH 1<br />

Card power supply V DC 5 internal through bus 5 internal through bus<br />

External output voltage supply V DC 24 24<br />

Tolerance +20 %/-15 % +20 %/-15 %<br />

Residual ripple % F 5 F 5<br />

Protection against polarity reversal Yes Yes<br />

Current consumption<br />

Logic 5 V bus mA Normally 150 Normally 85<br />

External 24 V (no-load) mA Normally 230 Normally 70<br />

Power loss<br />

Logic 5 V bus W Approx. 0.74 Approx. 0.425<br />

External 24 V W Approx. 5.6 Approx. 4.5<br />

Outputs<br />

Number 16 8<br />

Rated current<br />

per output at Ue = 24 V Ie A 0.5 2<br />

Isolation between output and 5 V logic bus Yes Yes<br />

Terminals Plug-in screw terminal Plug-in screw terminal<br />

Terminal capacity mm 2 1.5 1.5<br />

Indication elements LED LED<br />

Short-circuit trip With manual reset<br />

Short-circuit trip, control mode 1 With manual reset<br />

Short-circuit trip, control mode 2 With automatic reset<br />

Parallel connection of outputs per card (per group) Max. 4 No<br />

Indication of monitoring activity<br />

LED Yes Yes<br />

ZAA Low active Low active<br />

Residual current on “Off” signal mA 300 400<br />

Signal range at Ue<br />

“Off” signal V 2.5 2<br />

"On" signal = rated voltage = rated voltage<br />

Rated current<br />

per output at Ue = 24 V Ie A 0.5 2<br />

per output at Umax Ie A 0.6 2.4<br />

Delay time<br />

On 0 V r 24 V ms 60 60<br />

Off 24 V r 0 V ms 100 700<br />

Utilization factor g % 1 1<br />

Duty factor % DF 100 100<br />

Monitoring<br />

Short-circuit Yes Yes, with manual reset<br />

Thermal Yes<br />

Overload Yes<br />

Operating frequency at inductive load To DC-13 To DC-13<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616