http://catalog.moeller.net <strong>Moeller</strong> HPL0211-2007/2008<br />

Technical Data<br />

Analog input/output cards<br />

Analog input/output card PS416-AIN-400 PS416-AIO-400<br />

General<br />

Standards EN 61131-2, EN 50178 EN 61131-2, EN 50178<br />

Ambient temperature °C 0…55 0…55<br />

Ambient temperature, storage °C –25…70 –25…70<br />

Weight kg 0.2 0.2<br />

Space requirement 4 space units = 1 slot 4 space units = 1 slot<br />

Electromagnetic compatibility (EMC) a Page 4/143 a Page 4/143<br />

Protection class 1 1<br />

Protection type IP20 IP20<br />

Cards per BGT Number Max. 8/11 (limited by power supply<br />

unit)<br />

Power supply for PS416 bus V DC 5/max. 700 mA 5/max. 1 A<br />

External power supply Not applicable Not applicable<br />

Analog I/O to PS416 bus V AC 600 600<br />

Max. 6/8 (limited by power supply<br />

unit)<br />

Inputs/outputs<br />

Potential isolation to PS416 internal bus to PS416 internal bus<br />

Input channels Qty. 8 4<br />

Output channels Qty. – 4<br />

Input voltage range<br />

Channel 0 – 3 V g 5<br />

0 – 5<br />

g 10<br />

0 – 10<br />

Channel 4 – 7 V 0 … 1<br />

Input/output voltage range V g 5<br />

0 – 5<br />

g 10<br />

0 – 10<br />

Voltage range setting<br />

Channel 0 – 3 Via software from PLC<br />

Channel 4 – 7 Fixed 0 – 1 V<br />

All channels Via software from PLC<br />

Input range current mA 0 … 20<br />

4 … 20<br />

Input/output current ranges: mA 0 … 20<br />

4 … 20<br />

Current range setting Via software from PLC Via software from PLC<br />

Current/voltage selection per channel Via selector switch Via selector switch, wiring<br />

Input channel measuring principle Successive approximation Successive approximation<br />

Resolution<br />

g10 V, 0 – 10 V Bit 12 12<br />

g 5 V, 0 – 5 V Bit 12 11 (outputs)<br />

12 (inputs)<br />

0 … 1 V Bit 12 –<br />

0 … 20 mA Bit 12 12<br />

4 … 20 mA Bit 11 11<br />

Outputs short-circuit/overload proof Yes<br />

Accuracy<br />

Differential non-linearity 0 – 55 °C LSB < 1 (all ranges) < 1 (all ranges)<br />

Total error, voltage and current outputs (0 – 55 °C) % Normally 0.4 Normally 0.4<br />

Deviation due to EMC interference % Max. 10 (interference class 3) Max. 10 (interference class 3)<br />

Conversion time<br />

Inputs (8/12-bit) ms 1.6 – 14 1.6 – 7.6<br />

Outputs (12-bit) ms – 1.6 – 2.8<br />

Load on voltage outputs kO – 2<br />

Load on current outputs O – f 560<br />

Input impedance, voltage inputs > 100 kO, 56 pF > 100 kO, 56 pF<br />

Input impedance, current inputs O 50 50<br />

Data output With image register With image register<br />

Scan time/averaging Adjustable through S 40 Topology<br />

Configurator<br />

PS416-AI…<br />

Adjustable through S 40 Topology<br />

Configurator<br />

Notes All error specifications are in relation to the respective range.<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616<br />