easy relay, easy MFD, easy <strong>Control</strong><br />

4/72<br />

Technical Data<br />

Ethernet Gateway, Upstream devices, SmartWire modules<br />

EASY2…<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

http://catalog.moeller.net<br />

EASY209-SE EASY223-SWIRE<br />

Power supply<br />

Rated operational voltage Ue V 24 (-15/+20 %) 24 (-15/+20 %)<br />

Admissible range V DC 20.4…28.8 20.4…28.8<br />

Residual ripple % 5 5<br />

max. current consumption (at 24 V DC) mA Normally 65 Normally 100 + n x 30<br />

n = Number of stations<br />

Voltage dips (IEC/EN 61131-2) ms 10<br />

Heat dissipation at 24 V DC W 1.7W<br />

Supply voltage UAUX (power supply for switching SmartWire<br />

elements, e.g. contactor coils)<br />

Rated operational voltage UAux V DC 24, –15 %, +20 % (Derating above > 40 °C)<br />

Admissible range 20.4…28.8<br />

at 45 °C: 21.0…28.8<br />

at 50 °C: 21.6…28.8<br />

at 55 °C: 22.2…27.6<br />

Max. current consumption (at 24 V DC) mA Normally 3<br />

Residual ripple % < 5<br />

Voltage dips (IEC/EN 61131-2) ms 10<br />

Short-circuit on the SmartWire end No. 3 A external protection necessary. MCB<br />

FAZ-Z3<br />

Supply voltage UGateway (supply voltage Gateway <strong>Electronic</strong><br />

and SmartWire element electronics)<br />

Rated operating voltage UGateway V DC 24 (-15/+20 %)<br />

Admissible range V DC 20.4 … 28.8<br />

Max. current consumption (at 24 V DC) A Normally 500 (normally 100 gateways +<br />

normally 25 per controller wiring module)<br />

Residual ripple % F 5<br />

Voltage dips (IEC/EN 61131-2) ms 10<br />

Heat dissipation at 24 V DC W Normally 14 (normally 4 gateways + normally<br />

0.6 per controller wiring module)<br />

Short-circuit on the SmartWire end Yes<br />

Protection against polarity reversal<br />

AS-I power supply Yes Yes<br />

LEDs<br />

Supply Front power LED: ON<br />

LED display Front-LED COM active: flashing<br />

RJ 45 socket, top No Activity: OFF, Amber: Half Duplex, Green: Full<br />

Duplex<br />

RJ 45 socket, bottom No Link: OFF, Amber: 10 MBit/s, Green: 100<br />

MBit/s<br />

Gateway ready for operation Ready: green<br />

Power supply SmartWire (contactor) UAUX: green<br />

Network Status (easyNET/CANopen) Bus: green/red<br />

Status SmartWire SmartWire: green<br />

Reset Front: via buttons > 2s<br />

Strain relief Via cable binders in retaining nipples<br />

Network<br />

Connection technique RJ45, 8-pole<br />

Potential isolation Yes, for UAUX, UGATEWAY, SmartWire<br />

Bus protocol a page 4/35<br />

Bus terminating resistors External, first and last station<br />

Bus addresses Factory settings Ethernet: IP address 0.0.0.0<br />

SUBNET mask: 255.255.0.0 Gateway address<br />

0.0.0.0 Remote address 0.0.0.0<br />

easy-NET: 2 … 8, adjustable via easyNet<br />

configutarion (station 1) or terminal mode<br />

CANopen: 1 … 126, adjustable via DIP<br />

switches<br />

SmartWire<br />

Connection types Plug, 6 pole<br />

Data/power cable 6 core flat-band cable<br />

Maximum cable length (gateway to last<br />

station)<br />

m 4<br />

Bus termination (last station) Termination connector<br />

Slave address allocation via SmartWire gateway<br />

Potential isolation none<br />

Station Max. 16, via SmartWire gateway<br />