Switched-mode power supply units,<br />
power supply units<br />
4/156<br />
Technical Data<br />
Switched-mode power supply units<br />
SN3<br />
SN3-000-MMEU8<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
General<br />
Standards IEC 61204<br />
73/23/EWG<br />
89/336/EWG<br />
EN 50178, EN 60950, UL 60950, UL 508<br />
Duty factor % 100<br />
Dimensions (W x H x D) mm 56,25 x 54 x 24 (when mounted)<br />
Weight kg 0.065<br />
Terminal capacities<br />
Flexible with ferrule mm 2 0.2…2.5 (22…14 AWG)<br />
Flexible without ferrule mm 2 0.2…2.5 (22…14 AWG)<br />
Massive mm 2 0.2…4 (22…14 AWG)<br />
Degree of protection<br />
Enclosures IP20<br />
Terminals IP20<br />
Protection class 2<br />
Mounting Plugged into power supply unit<br />
Fixing Snap fastener, tool-less<br />
Vibrations (IEC/EN 60068-2-6) 1…57 Hz, amplitude g0.075 mm, 57…100 Hz, 5 g<br />
Mechanical shock resistance (IEC 60068-2-27) 5 g all directions<br />
Environmental compatibility<br />
Ambient temperature<br />
Operation °C –25…+70<br />
Storage °C –40…+85<br />
Climatic proofing 93% at +40°C according to IEC 60068-2-3, no condensation<br />
Climatic class (IEC) 3K3 according to EN 60721<br />
Insulation voltage<br />
Rated insulation voltage Ui V AC 250 according to IEC 60974-1, EN 50178, VDE 0160<br />
Power supply/measuring circuit/relay outputs Safe isolation according to EN 50178, EN 60950<br />
Rated impulse withstand voltage between all<br />
insulated circuits<br />
Uimp kV 4 according to IEC 664, VDE 0110<br />
Test voltage between all circuits kV 2.5 AC (routine test)<br />
Overvoltage category/pollution degree according to EN 60950, Class 2<br />
Input circuit<br />
Rated input voltage V 110…240 AC / 100…350 DC<br />
(supplied from the input circuit of the power supply)<br />
Input voltage range V 70…264 AC<br />
Input voltage range V 80…350 DC<br />
Power consumption VA 2.5<br />
Power consumption W 1.5<br />
REMOTE-OFF input<br />
Switch off<br />
potential-free<br />
R F 1 kO<br />
Switching on R f 10 kO<br />
Input current mA typically 1 (200 mA for 200 ms)<br />
Cable length m 25<br />
Measuring circuits<br />
INPUT<br />
Monitoring function Undervoltage monitoring<br />
Threshold values 85 V AC/90 V DC<br />
Accuracy/tolerance % -5 % for AC and DC<br />
Hysteresis with respect to the threshold value typically -8 % for AC and -30 % for DC<br />
Measuring cycle max. ms Normally F 50<br />
OUTPUT<br />
Monitoring function Undervoltage monitoring<br />
Threshold values 20 V DC<br />
Accuracy/tolerance % 1<br />
Hysteresis with respect to the threshold value % Normally 5<br />
Measuring cycle max. ms Normally F 10<br />