http://catalog.moeller.net <strong>Moeller</strong> HPL0211-2007/2008<br />
Technical Data<br />
Bus modules<br />
Analog EM4 EM4-101-AA2 EM4-101-TX1 EM4-101-TX2<br />
Analog inputs<br />
Number 8 (4V/4I) 2 V<br />
Signal ranges 0 – 5 V<br />
0 – 10 V<br />
g 5V<br />
g 10 V<br />
0 – 20 mA<br />
0 – 10 V<br />
Potential isolation Yes, inputs from earthing point, 24 V DC supply voltage, and bus, not inputs from each other (nor outputs<br />
in the case of AA2/AA1)<br />
Connection type of signal encoder Two-wire connection to transducer<br />
Resolution<br />
Permissible potential difference<br />
Bit 8/12 12<br />
Between inputs Not permissible<br />
Between inputs and central earth point See Rated insulation voltage<br />
Input current<br />
Range 0 to 20 mA mA 30 – –<br />
Permissible input voltage V max. g 15 +20 (destruction limit)<br />
Error indication on overrange Yes<br />
Total error % Normally 0.4 of full scale Normally 0.5 of full scale<br />
Cable length screened m < 50 for cable cross-section f<br />
0.14 mm2 Input impedance<br />
< 20 –<br />
0 to 5 V kO > 100 kO per input<br />
0 to 10 V kO > 100 kO per input 20 kO<br />
-5 to 5 V kO > 100 kO per input<br />
-10 to 10 V kO > 100 kO per input<br />
0 to 20 mA O 50 O per input<br />
Analog inputs<br />
Quantity 6 temperature inputs for Pt 100/Ni<br />
1000<br />
Connection type 3 or 4-wire connection<br />
Temperature range °C Pt 100: -100 to +300 °C Ni 1000: -<br />
50 to +150 °C<br />
Deviation Pt 100: max. g 0.4 %; typically g<br />
0.2 % Ni 1000: max. g 0.2 %;<br />
typically g 0.1 %<br />
Linearity factor Pt 100: max. g 0.15 % Ni 1000:<br />
max. g 0.1 %<br />
Reproducibility (with steady state at 25 °C) Pt 100: max. g 0.3 °C Ni 1000:<br />
max. g 0.2 °C<br />
Pt 100: max. g 0.3 °C Ni 1000:<br />
max. g 0.2 °C<br />
Error indication Detection of cable break and shortcircuit<br />
R0 to R5 short-circuit-proof Yes<br />
Analog outputs<br />
Number 4 – –<br />
Signal ranges 0 – 10 V<br />
g 10 V<br />
Potential isolation Yes, of inputs from earthing<br />
point 24 V DC supply and bus,<br />
not between inputs and<br />
outputs<br />
Resolution Bit 8/12<br />
Total error % Normally 0.4 of full scale<br />
Connection type Two-wire connection<br />
Short-circuit proof Yes<br />
Short-circuit current mA 32<br />
Permissible potential difference between<br />
earthing point and between outputs<br />
See Rated insulation voltage<br />
Cable length, screened m < 50 for cable cross-section f<br />
0.14 mm2 – –<br />
Rated insulation voltage O 2000 – –<br />
6 for thermocouple types J, K, L<br />
4/131<br />
J: 0 to 1200 °C K: 0 to 1300 °C L: 0<br />
to 900 °C<br />
Converter: max. 0.5 % of preset<br />
final value Cold junction: max. 4 °C<br />
max. 0.4 °C<br />
Wire-break and overrange/<br />
underrange detection<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616<br />
EM4<br />
Compact PLC PS4