http://catalog.moeller.net <strong>Moeller</strong> HPL0211-2007/2008<br />

Technical Data<br />

Bus modules<br />

Analog EM4 EM4-101-AA2 EM4-101-TX1 EM4-101-TX2<br />

Analog inputs<br />

Number 8 (4V/4I) 2 V<br />

Signal ranges 0 – 5 V<br />

0 – 10 V<br />

g 5V<br />

g 10 V<br />

0 – 20 mA<br />

0 – 10 V<br />

Potential isolation Yes, inputs from earthing point, 24 V DC supply voltage, and bus, not inputs from each other (nor outputs<br />

in the case of AA2/AA1)<br />

Connection type of signal encoder Two-wire connection to transducer<br />

Resolution<br />

Permissible potential difference<br />

Bit 8/12 12<br />

Between inputs Not permissible<br />

Between inputs and central earth point See Rated insulation voltage<br />

Input current<br />

Range 0 to 20 mA mA 30 – –<br />

Permissible input voltage V max. g 15 +20 (destruction limit)<br />

Error indication on overrange Yes<br />

Total error % Normally 0.4 of full scale Normally 0.5 of full scale<br />

Cable length screened m < 50 for cable cross-section f<br />

0.14 mm2 Input impedance<br />

< 20 –<br />

0 to 5 V kO > 100 kO per input<br />

0 to 10 V kO > 100 kO per input 20 kO<br />

-5 to 5 V kO > 100 kO per input<br />

-10 to 10 V kO > 100 kO per input<br />

0 to 20 mA O 50 O per input<br />

Analog inputs<br />

Quantity 6 temperature inputs for Pt 100/Ni<br />

1000<br />

Connection type 3 or 4-wire connection<br />

Temperature range °C Pt 100: -100 to +300 °C Ni 1000: -<br />

50 to +150 °C<br />

Deviation Pt 100: max. g 0.4 %; typically g<br />

0.2 % Ni 1000: max. g 0.2 %;<br />

typically g 0.1 %<br />

Linearity factor Pt 100: max. g 0.15 % Ni 1000:<br />

max. g 0.1 %<br />

Reproducibility (with steady state at 25 °C) Pt 100: max. g 0.3 °C Ni 1000:<br />

max. g 0.2 °C<br />

Pt 100: max. g 0.3 °C Ni 1000:<br />

max. g 0.2 °C<br />

Error indication Detection of cable break and shortcircuit<br />

R0 to R5 short-circuit-proof Yes<br />

Analog outputs<br />

Number 4 – –<br />

Signal ranges 0 – 10 V<br />

g 10 V<br />

Potential isolation Yes, of inputs from earthing<br />

point 24 V DC supply and bus,<br />

not between inputs and<br />

outputs<br />

Resolution Bit 8/12<br />

Total error % Normally 0.4 of full scale<br />

Connection type Two-wire connection<br />

Short-circuit proof Yes<br />

Short-circuit current mA 32<br />

Permissible potential difference between<br />

earthing point and between outputs<br />

See Rated insulation voltage<br />

Cable length, screened m < 50 for cable cross-section f<br />

0.14 mm2 – –<br />

Rated insulation voltage O 2000 – –<br />

6 for thermocouple types J, K, L<br />

4/131<br />

J: 0 to 1200 °C K: 0 to 1300 °C L: 0<br />

to 900 °C<br />

Converter: max. 0.5 % of preset<br />

final value Cold junction: max. 4 °C<br />

max. 0.4 °C<br />

Wire-break and overrange/<br />

underrange detection<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616<br />