http://catalog.moeller.net <strong>Moeller</strong> HPL0211-2007/2008<br />

MFD-R16<br />

MFD-T16<br />

MFD-R…<br />

MFD-T…<br />

MFD-T(A)P<br />

Analog inputs<br />

Number<br />

<strong>Electric</strong>al isolation<br />

4 (I7, I8, I11, I12)<br />

2 (I11, I12) for MFD-<br />

T(A)P<br />

To power supply No<br />

From the digital inputs No<br />

To the outputs Yes<br />

From the PC interface, memory card, NET network,<br />

EASY-Link<br />

Yes<br />

Input type DC voltage<br />

Signal range V DC 0 – 10<br />

Resolution, analog V 0.01<br />

Resolution, digital V 0.01<br />

Resolution Bit 10<br />

(value 0 – 1023)<br />

Input impedance<br />

Accuracy of actual value<br />

kO 11.2<br />

2 MFD devices % g 3<br />

Within a single device % g 2<br />

Conversion time, analog/digital ms Every CPU cycle<br />

Input current mA < 1<br />

Cable length screened m < 30<br />

Technical data<br />

I/O modules<br />

MFD-RA17<br />

MFD-TA17<br />

MFD-TAP<br />

Analog outputs<br />

Number<br />

<strong>Electric</strong>al isolation<br />

1 1<br />

To power supply No No<br />

From the digital inputs No No<br />

From the digital outputs Yes Yes<br />

From the PC interface, memory card,<br />

NET network, EASY-Link<br />

Yes Yes<br />

Output type DC voltage DC voltage<br />

Signal range V DC 0 – 10 0 – 10<br />

Max. output current A 0.01 0.01<br />

Load resistance 1 kO 1 kO<br />

Overload and short-circuit protection Yes Yes<br />

Resolution, analog V DC 0.01 0.01<br />

Resolution, digital Bit 10, (value: 0 – 12 (value 0…4095)<br />

1023)<br />

at QA01, MD<br />

Resolution, digital V DC – 0.1, 0.01, 0.001 at<br />

MD<br />

Recovery time ms 100 100<br />

Accuracy<br />

-25 °C – 55 °C % 2 2<br />

25°C % 1 1<br />

Conversion time Every CPU cycle Every CPU cycle<br />

MFD-TP, MFD-TAP<br />

Analog input temperature resistance Pt100 or Ni1000 sensors<br />

Number<br />

Input type resistance sensor<br />

Platinum sensor Pt100 according to DIN EN 60751, IEC 751<br />

Nickel sensor Ni1000 according to DIN 43760<br />

Temperature range<br />

2 x Pt100 or 2 x Nt1000 (jaccording to type)<br />

Pt100, Range A, selectable °C , (°F) –40 to +90, (-40 to 194); 0 to 250, (32 to 482); 0 to 400, (32 to 752)<br />

Ni1000, Range A, selectable °C , (°F) –40 to +90, (-40 to 194); 0 to 250, (32 to 482)<br />

Pt100, Range B<br />

<strong>Electric</strong>al isolation<br />

°C , (°F) 0 to 850, (32 to 1562); - 200 to 200, (–328 to 392)<br />

To power supply No<br />

From the digital inputs No<br />

To the outputs Yes<br />

From the PC interface, memory card, NET network, EASY-Link<br />

Resolution digital, scaling per sensor<br />

Yes<br />

With operands "IA" and "MD", selectable under scaling Bit 12 (0 to 4095)<br />

With operand "MD", selectable under scaling °C, (°F) 1, 0.1, (1), (0.1)<br />

Measuement value resolution analog/digital Bit Depending upon the scaling<br />

Measuring current mA < 1.6<br />

Damage limit (in the case of a wiring error) Apply external voltage<br />

Measurement method<br />

Accuracy (without EMC interference)<br />

Two or three wire per sensor, selectable by connection of sensor<br />

Two MFD devices one above the other % Typically 1; maximal 1.6 (Pt); 1.2 (Ni)<br />

Pt100-sensor (Offset error, linearity error, repetition accuracy, temperature<br />

dependency of the device included)<br />

% g0.8 of measurement range<br />

Ni1000-sensor (Offsetf error, linearity error, repetition accuracy, temperature<br />

dependency of the device include)<br />

Conversion time, analog/digital<br />

% g0.6 of measurement range<br />

Without sampling time setting, selectable per sensor ms 200<br />

With sampling time (adjustable), selectable per sensor<br />

Additional measurement aids<br />

ms 200 to 65535<br />

Filterung (Software), smoothing of analog input signals<br />

(PT1 behaviour), only with set sampling time, selectable per sensor<br />

Yes<br />

. Filter for the suppression of certain frequencies and their multiples<br />

Diagnostics<br />

Hz 50, 60, 250, 500<br />

Card diagnostic Yes<br />

Wire break diagnostic per sensor Yes<br />

Wire break diagnostic per sensor Yes<br />

Below lower measurement range Yes<br />

Above upper measurement range Yes<br />

Cable length screened m < 10<br />

MFD...<br />

For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616<br />

4/61<br />

easy MFD

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!