MFD-R16<br />
MFD-T16<br />
MFD-R…<br />
MFD-T…<br />
MFD-T(A)P<br />
Analog inputs<br />
Number<br />
<strong>Electric</strong>al isolation<br />
4 (I7, I8, I11, I12)<br />
2 (I11, I12) for MFD-<br />
T(A)P<br />
To power supply No<br />
From the digital inputs No<br />
To the outputs Yes<br />
From the PC interface, memory card, NET network,<br />
EASY-Link<br />
Yes<br />
Input type DC voltage<br />
Signal range V DC 0 – 10<br />
Resolution, analog V 0.01<br />
Resolution, digital V 0.01<br />
Resolution Bit 10<br />
(value 0 – 1023)<br />
Input impedance<br />
Accuracy of actual value<br />
kO 11.2<br />
2 MFD devices % g 3<br />
Within a single device % g 2<br />
Conversion time, analog/digital ms Every CPU cycle<br />
Input current mA < 1<br />
Cable length screened m < 30<br />
Technical data<br />
I/O modules<br />
MFD-RA17<br />
MFD-TA17<br />
MFD-TAP<br />
Analog outputs<br />
Number<br />
<strong>Electric</strong>al isolation<br />
1 1<br />
To power supply No No<br />
From the digital inputs No No<br />
From the digital outputs Yes Yes<br />
From the PC interface, memory card,<br />
NET network, EASY-Link<br />
Yes Yes<br />
Output type DC voltage DC voltage<br />
Signal range V DC 0 – 10 0 – 10<br />
Max. output current A 0.01 0.01<br />
Load resistance 1 kO 1 kO<br />
Overload and short-circuit protection Yes Yes<br />
Resolution, analog V DC 0.01 0.01<br />
Resolution, digital Bit 10, (value: 0 – 12 (value 0…4095)<br />
1023)<br />
at QA01, MD<br />
Resolution, digital V DC – 0.1, 0.01, 0.001 at<br />
MD<br />
Recovery time ms 100 100<br />
Accuracy<br />
-25 °C – 55 °C % 2 2<br />
25°C % 1 1<br />
Conversion time Every CPU cycle Every CPU cycle<br />
MFD-TP, MFD-TAP<br />
Analog input temperature resistance Pt100 or Ni1000 sensors<br />
Number<br />
Input type resistance sensor<br />
Platinum sensor Pt100 according to DIN EN 60751, IEC 751<br />
Nickel sensor Ni1000 according to DIN 43760<br />
Temperature range<br />
2 x Pt100 or 2 x Nt1000 (jaccording to type)<br />
Pt100, Range A, selectable °C , (°F) –40 to +90, (-40 to 194); 0 to 250, (32 to 482); 0 to 400, (32 to 752)<br />
Ni1000, Range A, selectable °C , (°F) –40 to +90, (-40 to 194); 0 to 250, (32 to 482)<br />
Pt100, Range B<br />
<strong>Electric</strong>al isolation<br />
°C , (°F) 0 to 850, (32 to 1562); - 200 to 200, (–328 to 392)<br />
To power supply No<br />
From the digital inputs No<br />
To the outputs Yes<br />
From the PC interface, memory card, NET network, EASY-Link<br />
Resolution digital, scaling per sensor<br />
Yes<br />
With operands "IA" and "MD", selectable under scaling Bit 12 (0 to 4095)<br />
With operand "MD", selectable under scaling °C, (°F) 1, 0.1, (1), (0.1)<br />
Measuement value resolution analog/digital Bit Depending upon the scaling<br />
Measuring current mA < 1.6<br />
Damage limit (in the case of a wiring error) Apply external voltage<br />
Measurement method<br />
Accuracy (without EMC interference)<br />
Two or three wire per sensor, selectable by connection of sensor<br />
Two MFD devices one above the other % Typically 1; maximal 1.6 (Pt); 1.2 (Ni)<br />
Pt100-sensor (Offset error, linearity error, repetition accuracy, temperature<br />
dependency of the device included)<br />
% g0.8 of measurement range<br />
Ni1000-sensor (Offsetf error, linearity error, repetition accuracy, temperature<br />
dependency of the device include)<br />
Conversion time, analog/digital<br />
% g0.6 of measurement range<br />
Without sampling time setting, selectable per sensor ms 200<br />
With sampling time (adjustable), selectable per sensor<br />
Additional measurement aids<br />
ms 200 to 65535<br />
Filterung (Software), smoothing of analog input signals<br />
(PT1 behaviour), only with set sampling time, selectable per sensor<br />
Yes<br />
. Filter for the suppression of certain frequencies and their multiples<br />
Diagnostics<br />
Hz 50, 60, 250, 500<br />
Card diagnostic Yes<br />
Wire break diagnostic per sensor Yes<br />
Wire break diagnostic per sensor Yes<br />
Below lower measurement range Yes<br />
Above upper measurement range Yes<br />
Cable length screened m < 10<br />
MFD...<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616<br />
4/61<br />
easy MFD