http://catalog.moeller.net <strong>Moeller</strong> HPL0211-2007/2008<br />

Technical Data<br />

Switched-mode power supply units<br />

4/155<br />

SN3-050-BU8 SN3-100-BV8 SN3-200-BV8 SN3-050-EU8 SN3-100-EU8 SN3-200-EU8<br />

Input circuit<br />

Rated input voltage V 110…240 AC 110…240 AC 110…240 AC 110…240 AC<br />

Switch position 110 V – 110-120 AC 110-120 AC – – –<br />

Switch position 230 V – 220-240 AC 220-240 AC – – –<br />

Input voltage range V 85…264 AC – – 85…264 AC 85…264 AC 85…264 AC<br />

Input voltage range V 100…350 DC – – 100…350 DC 100…350 DC 100…350 DC<br />

Switch position 110 V AC V – 85-132 AC 85-132 AC – – –<br />

Switch position 230 V AC V – 184-264 AC 184-264 AC – – –<br />

Switch position 230 V DC V – 220-350 DC 220-350 DC – – –<br />

Supply frequency<br />

Rated value Hz 50/60 50/60 50/60 50/60 50/60 50/60<br />

Range Hz 47…63 47…63 47…63 47…63 47…63 47…63<br />

Current consumption<br />

At 110 … 240 V AC A Approx.<br />

2.2…1.2<br />

Switch position 110 V AC A Approx. – Approx.<br />

4.2…4.0<br />

Switch position 230 V AC A Approx. – Approx.<br />

2.4…2.2<br />

Approx. – Approx. – Approx.<br />

2.2…1.2<br />

Approx.<br />

9.0…8.0<br />

Approx.<br />

4.4…4.0<br />

Approx.<br />

3.5…1.6<br />

Approx.<br />

5.5…2.5<br />

Approx. – Approx. – Approx. –<br />

Approx. – Approx. – Approx. –<br />

Power consumption W Normally 135 Normally 269 Normally 538 Normally 135 Normally 269 Normally 538<br />

Inrush current limiter/i 2t (cold start) F 23 A /<br />

approx. 0.9 A 2s<br />

F 40 A /<br />

approx. 1.8 A 2s<br />

F 70 A /<br />

approx. 8 A 2s<br />

F 23 A /<br />

approx. 0.9 A 2s<br />

F 33 A /<br />

approx. 0.2 A 2s<br />

F 40 A /<br />

approx. 1.9 A 2s<br />

Mains failure bridging ms typically f 100 typically f 50 typically f 50 typically f 100 typically f 40 typically f 40<br />

Run-up time after mains voltage applied ms Normally f<br />

100<br />

Normally f 10 Normally f 20 Normally f<br />

100<br />

Normally f 5 Normally f<br />

370<br />

Transient overvoltage protection Varistors Varistors Varistors Varistors Varistors Varistors<br />

Internal input fuse (device protection, not<br />

accessible)<br />

4 AT 6.3 AT 12 AF 4 AT 6.3 AT 12 AF<br />

Discharge current to PE mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA < 3.5 mA<br />

Output circuit<br />

L+, L+, L-, L- Proof against short-circuit, no-load and overload<br />

Rated output voltage V 24 DC 24 DC 24 DC 24 DC 24 DC 24 DC<br />

Tolerance -1…+5 % -1…+5 % -1…+5 % -1…+5 % -1…+5 % -1…+5 %<br />

Setting range for the output voltage fixed 24 V DC fixed 24 V DC fixed 24 V DC 22…28 V DC; ex-works set to 24 V g0.5%<br />

Rated output power W 120 240 480 120 240 480<br />

Rated output current Tu F 60 °C A 5 10 20 5 10 20<br />

Peak output current (power reserves) Tu F 40 °C A Normally F<br />

7.25<br />

Normally F<br />

12.25<br />

Normally F<br />

22.5<br />

Normally F<br />

7.25<br />

Normally F<br />

12.25<br />

Normally F<br />

22.5<br />

Derating 60 °C F Tu F 70 °C<br />

<strong>Control</strong> deviation at<br />

2.5 % per Kelvin temperature increase<br />

Load change 10…90 %, static Normally<br />

g0.1 % g0.1 % g0.1 % g0.05 % g0.05 % g0.05 %<br />

Load change 10…90 %, dynamic Normally<br />

g3 % g3 % g3 % g3 % g3 % g3 %<br />

<strong>Control</strong>ler acting time ms Normally 1 Normally 1 Normally 1 Normally 1 Normally 1 Normally 1<br />

Input voltage deviation g10 % Normally g0.05 % Normally g0.05 % Normally g0.05 % Normally g0.05 % Normally g0.05 % Normally g0.05 %<br />

Rise time 10…90 % ms Normally F 30 Normally F 5 Normally F 15 Normally F 30 Normally F 4 Normally F 12<br />

Residual ripple and switching peaks 20 MHz typically < 50 mVss<br />

Can be switched in parallel yes, up to 5 devices for redundancy and for power increase, non symetrical current<br />

Series connection capability yes, for voltage increase<br />

Resistance to reverse feed yes, limited to approx. 35 V AC<br />

Power factor correction (PFC) No Yes<br />

Status indication OUTPUT OK: LED green<br />

Overload characteristics a AWA2727-2317 (www.moeller.net/support) a AWA2727-2318 (www.moeller.net/support)<br />

Behaviour on short-circuit continuously with current limitation<br />

Current limitation at short-circuit A Approx. 11 Approx. 19 Approx. 25 Approx. 11 Approx. 19 Approx. 25<br />

Short-circuit protection Proof against sustained short circuit<br />

Overload protection thermal protection<br />

Capacitive load starting Not restricted<br />

Notes<br />

1) At U f 264 V DC additionally suitable, use external fuse.<br />