Modular PLC PS416<br />

4/148<br />

Technical Data<br />

Digital counter card<br />

PS416-CNT…, CM…<br />

Digital counter card PS416-CNT-200<br />

<strong>Moeller</strong> HPL0211-2007/2008<br />

General<br />

Standards EN 61131-2, EN 50178<br />

Ambient temperature °C 0…55<br />

Ambient temperature, storage °C –25…70<br />

Weight kg 0.35<br />

Space requirement 8 space units = 2 slots<br />

Electromagnetic compatibility (EMC) a Page 4/143<br />

Card power supply V DC 5 internal through bus<br />

Power consumption (bus end) mA Normally 350 (24 V DC external)<br />

Power consumption (external) mA 250<br />

Voltage range V DC 18 – 30<br />

Residual ripple Uss V 1.3<br />

Heat dissipation with full complement of modules fitted W 8<br />

Short-circuit protection<br />

Inputs<br />

1.6 A slow-blow/250 V<br />

Transducer power supply<br />

Current consumption of encoders<br />

V DC 24/5 g 1 % through card<br />

At 24 V DC mA 250<br />

At 5 V DC mA 100<br />

Counters per card Number F depending on the modules fitted<br />

Counter frequency kHz 0 – 50<br />

Potential isolation<br />

Rated insulation voltage<br />

Yes, between input modules and PS416 bus<br />

Power supply to rack V AC 1500<br />

Counter inputs to PS416 bus V AC 600<br />

Cable connection<br />

Max. permissible cable length, single-core from encoder to<br />

the module input<br />

m < 10 m on external interference (screened)<br />

> 10 m for the following installation conditions (see note):<br />

http://catalog.moeller.net<br />

Notes Cables made up from twisted pairs, common shielding, max. cross-section for connection 0.5 mm 2 .<br />

The max. possible cable length is determined by the signal levels that are required. The spacing between<br />

signal cables and power cables must be as large as feasible. The requirements and specifications of the<br />

manufacturers of the signal devices must be observed.<br />

Reverse counter modules Up/down counter module<br />

CM61.1 CM61.2 CM62.1 CM62.2<br />

Modules<br />

Inputs pulse form to DIN 19240 Square, triangular, sinusoidal Square, triangular, sinusoidal<br />

Two pulse sequences, offset by 90°<br />

Max. input voltage V DC 30 5 30 5<br />

Min. input voltage V DC 3 1 3 1<br />

Input current normally mA 1.6 0.33 1.6 0.33<br />

1 signal detection V 15 2 15 2<br />

0 signal detection V 5 1 5 1<br />

Space requirement per module 1 socket on the card 2 sockets on the card<br />