Modular PLC PS416<br />
4/148<br />
Technical Data<br />
Digital counter card<br />
PS416-CNT…, CM…<br />
Digital counter card PS416-CNT-200<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
General<br />
Standards EN 61131-2, EN 50178<br />
Ambient temperature °C 0…55<br />
Ambient temperature, storage °C –25…70<br />
Weight kg 0.35<br />
Space requirement 8 space units = 2 slots<br />
Electromagnetic compatibility (EMC) a Page 4/143<br />
Card power supply V DC 5 internal through bus<br />
Power consumption (bus end) mA Normally 350 (24 V DC external)<br />
Power consumption (external) mA 250<br />
Voltage range V DC 18 – 30<br />
Residual ripple Uss V 1.3<br />
Heat dissipation with full complement of modules fitted W 8<br />
Short-circuit protection<br />
Inputs<br />
1.6 A slow-blow/250 V<br />
Transducer power supply<br />
Current consumption of encoders<br />
V DC 24/5 g 1 % through card<br />
At 24 V DC mA 250<br />
At 5 V DC mA 100<br />
Counters per card Number F depending on the modules fitted<br />
Counter frequency kHz 0 – 50<br />
Potential isolation<br />
Rated insulation voltage<br />
Yes, between input modules and PS416 bus<br />
Power supply to rack V AC 1500<br />
Counter inputs to PS416 bus V AC 600<br />
Cable connection<br />
Max. permissible cable length, single-core from encoder to<br />
the module input<br />
m < 10 m on external interference (screened)<br />
> 10 m for the following installation conditions (see note):<br />
http://catalog.moeller.net<br />
Notes Cables made up from twisted pairs, common shielding, max. cross-section for connection 0.5 mm 2 .<br />
The max. possible cable length is determined by the signal levels that are required. The spacing between<br />
signal cables and power cables must be as large as feasible. The requirements and specifications of the<br />
manufacturers of the signal devices must be observed.<br />
Reverse counter modules Up/down counter module<br />
CM61.1 CM61.2 CM62.1 CM62.2<br />
Modules<br />
Inputs pulse form to DIN 19240 Square, triangular, sinusoidal Square, triangular, sinusoidal<br />
Two pulse sequences, offset by 90°<br />
Max. input voltage V DC 30 5 30 5<br />
Min. input voltage V DC 3 1 3 1<br />
Input current normally mA 1.6 0.33 1.6 0.33<br />
1 signal detection V 15 2 15 2<br />
0 signal detection V 5 1 5 1<br />
Space requirement per module 1 socket on the card 2 sockets on the card<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616