Electronic Relays, Relay, HMI, Control, PLCs ... - Moeller Electric Parts
Electronic Relays, Relay, HMI, Control, PLCs ... - Moeller Electric Parts
Electronic Relays, Relay, HMI, Control, PLCs ... - Moeller Electric Parts
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
http://catalog.moeller.net <strong>Moeller</strong> HPL0211-2007/2008<br />
Technical Data<br />
Power supply units, digital input cards<br />
PS416-POW-…, PS416-INP-…<br />
Power supply card PS416-POW-400 PS416-POW-410 PS416-POW-420<br />
General<br />
Standards EN 61131-2, EN 50178 EN 61131-2, EN 50178 EN 61131-2, EN 50178<br />
Ambient temperature °C 0…55 0…55 0…55<br />
Ambient temperature, storage °C –25…70 –25…70 –25…70<br />
Weight kg 0.74 0.74 0.74<br />
Space requirement 8 space units = 2 slots 8 space units = 2 slots 8 space units = 2 slots<br />
Electromagnetic compatibility (EMC) a Page 4/143 a Page 4/143 a Page 4/143<br />
Protection class 1 1 1<br />
Humidity class RH 1 RH 1 RH 1<br />
Idle proof Yes Yes Yes<br />
Test voltage kV 2.5 0.85 2.5<br />
Mains overvoltage protection Yes Yes Yes<br />
Rated voltage Ue V 230 V AC 24 V DC 115 V AC<br />
Rated frequency Hz 47440 47440<br />
Rated current Ie A Max. 0.5 3 1<br />
Inrush current A up to 50 (2 ms) up to 45 (2 ms) up to 50 (2 ms)<br />
Output current A 1.5 – 8 1.5 – 10 1.5 – 8<br />
Efficiency % 75 75 75<br />
Active power factor 0.8 1 0.8<br />
Switching frequency kHz 66 70 66<br />
Mains failure bridging ms 10 10 10<br />
Repetition rate s 1 1 1<br />
Vibration resistance 10 – 150 Hz g 1 1 1<br />
Mechanical shock resistance, shock duration 11 ms g > 15 > 15 > 15<br />
Insulation test Ui V AC 1800<br />
Digital input card PS416-INP-400 PS416-INP-401<br />
General<br />
Standards EN 61131-2, EN 50178 EN 61131-2, EN 50178<br />
Ambient temperature °C 0…55 0…55<br />
Ambient temperature, storage °C –25…70 –25…70<br />
Weight kg 0.15 0.15<br />
Space requirement 4 space units = 1 slot 4 space units = 1 slot<br />
Electromagnetic compatibility (EMC) a Page 4/143 a Page 4/143<br />
Humidity class RH 1 RH 1<br />
Digital inputs, 24 V DC Number 16 16<br />
Potential isolation between inputs and 5 V logic bus Yes Yes<br />
Connection technique Plug-in screw terminal Plug-in screw terminal<br />
Terminal capacity mm 2 1.5 1.5<br />
Indicating elements LED LED<br />
Current consumption 5 V bus mA Normally 30 Normally 30<br />
Power loss<br />
Internal 5 V bus W 0.15 0.15<br />
External 16 x input W 5.8 5.8<br />
Rated voltage Ue V DC 24 24<br />
Rated current Ie mA 8.6 g 0.5 8.6 g 0.5<br />
Input impedance kO 2.8 2.8<br />
Voltage range at Ue<br />
“0” signal V -3 – 5 -3 – 5<br />
“1” signal V 15 – 30.2 15 – 30.2<br />
Current range at Ie<br />
“0” signal mA 0 – 0.6 0 – 0.6<br />
“1” signal mA 2.5 – 12 2.5 – 12<br />
Make/break delay Normally 3.0/3.0 (ms) Normally 0.2/0.3 (ms)<br />
Utilization factor g % 1 1<br />
Duty factor % DF 100 100<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616<br />
4/145<br />
Modular PLC PS416