http://catalog.moeller.net <strong>Moeller</strong> HPL0211-2007/2008<br />
Technical Data<br />
Bus modules<br />
Digital EM4 EM4-101-DD2 EM4-111-DR2 EM4-201-DX2 EM4-204-DX1<br />
Digital outputs<br />
Number 8 or 6 at 10 inputs 6 (<strong>Relay</strong>)<br />
Contacts Make<br />
Rated operational voltage<br />
Rated voltage Ue V 24 DC See switching current<br />
Admissible range V DC 20.4 – 28.8<br />
Max. ripple % F 5<br />
Protection against polarity reversal Yes<br />
Potential isolation Yes Yes<br />
Potential isolation in groups No 2 isolated outputs, 4<br />
outputs, each with 2<br />
groups of 2<br />
Contact protection None<br />
Minimum load<br />
Minimum load W – 10 – –<br />
at contact voltage V – 12 – –<br />
at contact current mA – > 100 – –<br />
Rated current<br />
at state "1" Ie A 0.5 A at 24 V DC<br />
Lamp load RLL W 4 without series<br />
resistor<br />
Utilization factor g % 1 1 – –<br />
Duty factor % DF 100 100 – –<br />
Residual current at state "0" mA Max. 300<br />
Response time ms – 10 – –<br />
Reset time ms – 15 – –<br />
Lifespan, mechanical Operations – 20000000 – –<br />
Switching current (resistive load)<br />
2 A/230 V AC Operations – 300000 – –<br />
2 A/24 V DC Operations – 900000 – –<br />
Switching current (inductive load)<br />
1 A/230 V AC-11 Operations – 300000 – –<br />
1 A/24 V DC-11 Operations – 100000 – –<br />
Short-circuit protection Yes, without manual<br />
reset<br />
No, external<br />
protection of relay<br />
contacts, max. 4 A<br />
fast fuse required<br />
Limitation of disconnect voltage with<br />
inductive loads<br />
Maximum operating frequency<br />
Yes<br />
With time constant L/R max. 72 ms Ops./h 4000 – – –<br />
With time constant L/R max. 15 ms Ops./h 10000 – – –<br />
Creepage and clearance distances Group C, 250 V AC to<br />
VDE 0110<br />
Insulation test voltage, contact/coil kV – 4 – –<br />
Status indication of outputs Yes (LED) Yes (LED)<br />
Rated insulation voltage Ui V AC – 2800 – –<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616<br />
EM4<br />
4/129<br />
Compact PLC PS4