Compact PLC PS4<br />
4/138<br />
Technical Data<br />
Local expansion modules<br />
LE4-…<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
Analog LE4 LE4-206-AA1 LE4-206-AA2<br />
General<br />
Standards IEC/EN 61131-2<br />
EN 50178<br />
IEC/EN 61131-2<br />
EN 50178<br />
Ambient temperature °C 0…55 0…55<br />
Ambient temperature, storage °C –25…70 –25…70<br />
Vibration resistance g Constant 1 g/f= 10 to 150 Hz Constant 1 g/f= 10 to 150 Hz<br />
Mechanical shock resistance, shock duration 11<br />
ms<br />
g > 15 > 15<br />
Electromagnetic compatibility (EMC) a Page 4/143 a Page 4/143<br />
Terminals<br />
Terminal capacities<br />
Plug-in screw terminals Plug-in screw terminals<br />
Solid mm2 0.22 – 2.5 0.22 – 2.5<br />
Flexible with ferrule mm2 0.22 – 1.5 0.22 – 1.5<br />
Rated insulation voltage Ui V AC 600 600<br />
Protection type IP20 IP20<br />
Weight kg 0.265 0.3<br />
Protection class 1 1<br />
Configuration Max. 2 LE in conjunction with PS 4-2xx-MM1,<br />
PS 4-341-MM1 or EM 4-204-DX1<br />
http://catalog.moeller.net<br />
Max. 2 LE in conjunction with PS 4-2xx-MM1,<br />
PS 4-341-MM1 or EM 4-204-DX1<br />
Analog inputs<br />
Number 4 4<br />
Input ranges g 10 V 0 to 20 mA, 4 to 20 mA<br />
Potential isolation Yes, between inputs and bus, not between inputs and outputs<br />
Connection type of signal encoder Two-wire connection to transducer<br />
Resolution<br />
Permissible potential difference<br />
Bit Possible setting; 12-bit (4096 units)/10-bit<br />
(1024 units)<br />
12-bit (4096 units)<br />
Between inputs and central earth point See Rated insulation voltage<br />
Permissible input voltage V max. g 15<br />
Error indication on overrange Yes Yes<br />
Error indication on open-circuit detection No Yes, at 4 to 20 mA<br />
Total error % Typically 0.8 % of full scale Normally 0.4 % of full-scale (0 to 55 °C)<br />
Cable length screened m < 50 for cable cross-section f 0.14 mm 2<br />
Input impedance 40 per input 0.05 per input<br />
Analog outputs<br />
Number 2 2<br />
Output range g 10 V 0 to 20 mA, 4 to 20 mA<br />
Potential isolation Yes, between outputs and bus, not between inputs and outputs<br />
Load impedance per output O 2000 500<br />
Connection type Two-wire connection<br />
Resolution Bit Possible setting; 12-bit (4096 units)/10-bit<br />
(1024 units)<br />
12-bit (4096 units)<br />
Short-circuit proof Yes<br />
Short-circuit current mA 32<br />
Permissible potential difference between<br />
earthing point and between outputs<br />
See Rated insulation voltage 600 V AC<br />
Total error % Typically 0.8 % of full scale Normally 0.4 % of full-scale (0 to 55 °C)<br />
Cable length screened m < 50 for cable cross-section f 0.14 mm2 For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616