Electronic Relays, Relay, HMI, Control, PLCs ... - Moeller Electric Parts
Electronic Relays, Relay, HMI, Control, PLCs ... - Moeller Electric Parts
Electronic Relays, Relay, HMI, Control, PLCs ... - Moeller Electric Parts
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
easy MFD<br />
4/56<br />
Technical Data<br />
Display/operating units, CPU, communication modules<br />
MFD-…<br />
<strong>Moeller</strong> HPL0211-2007/2008<br />
http://catalog.moeller.net<br />
MFD-80.. MFD-CP4... MFD-CP8.. MFD-AC-CP8..<br />
General<br />
Standards EN 61000-6-1/-2/-3/-4, IEC 60068-2-6, IEC 60068-2-27<br />
Dimensions (W x H x D) mm 86.5 x 86.5 x 21.5<br />
(with actuators) 86.5 x<br />
86.5 x 20 (without<br />
actuators)<br />
75 x 58 x 36.2 107.5 x 90 x 30 107.5 x 90 x 30<br />
Weight kg 0.13 0.164 0.145 0.145<br />
Mounting 2 x 22.5 mm, display<br />
fixed with 2 fixing<br />
rings.<br />
Wall thickness:<br />
without top-hat rail<br />
(CPU) 1 – 6 mm<br />
with top-hat rail 1 – 4<br />
mm<br />
Fitted onto the fixing<br />
shaft of the display<br />
Fitted on the fixing shaft of the display or on tophat<br />
rail according to IEC/EN 60715, 35 mm deep<br />
(without display)<br />
Terminal capacities<br />
Solid mm 2 0.2x4 (AWG 24 – 12)<br />
Flexible with ferrule mm 2 0.2x2.5 (AWG 24 – 12)<br />
Standard screwdriver mm 3.5 x 0.6 3.5 x 0.6<br />
Power supply<br />
Solid mm 2 0.2/4 (AWG 24 – 12)<br />
flexible with ferrules mm 2 0.2/2.5 (AWG 24 – 12)<br />
Standard screwdriver mm 3.5 x 0.6<br />
Data cable<br />
Solid mm 2 0.08x2.5 (AWG 28 – 12)<br />
Flexible with ferrule mm 2 0.08x1.5 (AWG 28 – 12)<br />
Climatic environmental conditions<br />
Operating ambient temperature °C -25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2<br />
Condensation Take appropriate measures to prevent condensation<br />
LCD display (clearly legible) °C -5…50…(-10 to 0<br />
when background<br />
lighting is switched on<br />
(continuous operation))<br />
Storage °C –40…70 –40…70 –40…70 –40…70<br />
Relative humidity, non-condensing (IEC/EN<br />
60068-2-30)<br />
% 5…95 5…95 5…95 5…95<br />
Air pressure (operation) hPa 795…1080 795…1080 795…1080 795…1080<br />
Ambient conditions, mechanical<br />
Pollution degree 3 2 2 2<br />
Degree of protection IEC/EN 60529<br />
Vibrations (IEC/EN 60068-2-6)<br />
IP65 IP 20 IP 20 IP 20<br />
Constant amplitude 0.15 mm Hz 10…57 10…57 10…57 10…57<br />
Constant acceleration 2 g Hz 57…150 57…150 57…150 57…150<br />
Mechanical shock resistance (IEC/EN 60068-2-<br />
27) semi-sinusoidal 15 g/11 ms<br />
Impacts 18 18 18 18<br />
Drop to IEC/EN 60068-2-31 Drop<br />
height<br />
mm 50 50 50 50<br />
Free fall, packaged (IEC/EN 60068-2-32) m 1 1 1 1<br />
Mounting position horizontal, vertical<br />
For <strong>Moeller</strong> <strong>Electric</strong> Sales and Support call KMparts.com (866) 595-9616