1. Press the SETUP button to enter the setup mode.<br />

2. Use the Function keys to find the setup function #20. Select Automatic mode. Press<br />

the ENTER button.<br />

3. Go to setup function #22. Set the vacuum level in kPa. Press the Enter button.<br />

4. Press the SETUP button to return to the RUN mode.<br />

The control case will now attempt to control the pumping rate of vacuum pump #2 to<br />

maintain the set vacuum pressure. If the leak rate of the repair is very small the pump may<br />

stay off operate for a few occasional pump cycles. If the leak rate of the repair is high the<br />

leaks should be plugged. A high leakage rate wastes energy and causes the pump to operate<br />

unnecessarily.<br />

NOTE: If the leak rate is less than 0.1 l/min at a low control vacuum (i.e. less than -45kPa,<br />

13.3 Inches Hg) the vacuum pressure may vary by 6 kPa or 1.8 Inches Hg.<br />

Providing a leak of 0.3l/min will allow better control of the vacuum at low vacuum levels.<br />

7.5.3 Automatic Mode, Programmed Vacuum Levels<br />

In Local mode, when running a temperature cycle from the control case, the vacuum will<br />

follow the vacuum steps set in setup #9, 11, 13, 15, 17 and 19. Automatic vacuum mode<br />

must be selected in setup function #20.<br />

7.5.3 Vacuum Alarms, Local mode<br />

1. Press the SETUP button to enter the setup mode.<br />

2. Use the Function keys to find the setup function #24, ENABLE VAC ALARM.<br />

Select Yes and press the ENTER button.<br />

3. Go to setup function #25 and select the sensor that is to be used for the alarm.<br />

4. Go to setup functions #26 and #27. Set the vacuum level in kPa for the high vacuum<br />

and the low vacuum alarms. Press the ENTER button.<br />

The alarm will be active if the vacuum level is above or below the vacuum set level by the<br />

amount set in setup functions #22 or #26 and #27.<br />

5. Press the SETUP button to return to the RUN mode.<br />

Page 31