100<br />
The following general information shall be recorded:<br />
• Nameplate data including make, model, size, <strong>and</strong> refrigerant, sufficient to completely<br />
identify the liquid chilling package<br />
• Electrical frequency in Hz<br />
• Compressor driver or input rotative speed (rpm) for open type compressors<br />
• Temperature <strong>of</strong> ambient air at cooler, ºF (ºC)<br />
• Actual voltage, <strong>and</strong> current in amperes, for each phase, <strong>of</strong> all electric motor drives<br />
• Date, time, <strong>and</strong> location <strong>of</strong> test<br />
• Names <strong>of</strong> test supervisor <strong>and</strong> witnessing personnel<br />
• Specified refrigerant<br />
• Operating charge <strong>of</strong> refrigerant, lb (kg)<br />
Cooling Tower Testing<br />
The NTT basic test for a cooling tower measures water flow, temperature both entering<br />
<strong>and</strong> leaving the tower, <strong>and</strong> electrical components. The performance test encompasses<br />
testing recommended by NTT or the Cooling Tower Institute (CTI). Establish the tower<br />
airflow by determining flow in pounds per hour, while CTI determines the tower airflow<br />
according<br />
to the fans’ brake horsepower.<br />
The NTT performance test is not dependent upon the tower manufacturer’s curves. A<br />
graph generated by the NTT performance test illustrates the cooling tower operation<br />
through a wide range <strong>of</strong> conditions.<br />
Cooling tower performance test must be specified as per the NTT Cooling Tower<br />
performance procedure or the CT1 test. Performance testing is over <strong>and</strong> above the basic<br />
testing <strong>of</strong> towers.<br />
Basic Test<br />
The st<strong>and</strong>ard test for cooling towers is shown on the Associated <strong>Air</strong> Balance Council’s<br />
“Cooling Tower Operation Test Report.” The procedure is to measure <strong>and</strong> record:<br />
• Design <strong>and</strong> actual flow <strong>of</strong> the water<br />
100