17.11.2012 Views

Balancing of a Water and Air System (PDF

Balancing of a Water and Air System (PDF

Balancing of a Water and Air System (PDF

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

80<br />

The entire water system must be operational: all inspections performed, final strainers<br />

installed <strong>and</strong> clean, all controls operational with all valves fully open. Set the system for<br />

balancing in the following manner:<br />

1. Determine the total coil flow <strong>and</strong> determine:<br />

2. Diversity-is there enough pumping capacity to provide 100% design water flow to each<br />

coil? If there is not enough pumping capacity to provide 100% design water flow to each<br />

coil, close the valves to the coils closest to the pump until the pump can provide 100%<br />

flow to the open coils. If there are three-way valves or a bypass valve in the system,<br />

observe that it is closed prior to balancing.<br />

3. Record the pump (s) model <strong>and</strong> serial number, the motor nameplate, the design gpm<br />

flow, <strong>and</strong> the design head. Record the variable frequency drive (VFD) data if installed.<br />

4. If a VFD is installed, set the VFD bypass for 100%. Verify the impeller size on each<br />

pump.<br />

5. Read <strong>and</strong> record the actual pump head <strong>and</strong> flow with actual motor amperage <strong>and</strong><br />

voltage. Record starter data <strong>and</strong> motor over-load protection devices size <strong>and</strong> rating.<br />

6. Set each pump to provide approximately 10% more water flow than designed.<br />

7. Record all flow meter nameplate data. Read all flow meter flows <strong>and</strong> pressure drops<br />

throughout the entire system, (ie. chillers, converters, coils, etc.), <strong>and</strong> establish flow<br />

using Equation 11.4.<br />

8. Starting with the coil having the greatest flow, adjust the coil to the design flow.<br />

9. Continue to proportion the water to each coil until all coils are balanced within ± 10%<br />

<strong>of</strong> design flow with the balancing valve <strong>of</strong> at least one coil remaining 100% open. If the<br />

system has diversity, close an equal amount <strong>of</strong> valves nearest to the pump <strong>and</strong> open the<br />

initially closed valves. Continue to proportion the water to each coil (starting with the coil<br />

closest to the pump) until all the coils are balanced within ± 10% <strong>of</strong> the design flow.<br />

10. Re-verify <strong>and</strong> record the final pump gpm <strong>and</strong> head, amperage <strong>and</strong> voltage <strong>of</strong> each<br />

pump (discharge valve position if the system does not have a variable frequency drive).<br />

When the system has a VFD <strong>and</strong> the VFD is at 100% with the discharge valve throttled to<br />

obtain design flow, it is recommended that the impeller be trimmed or the VFD limited<br />

with the discharge valve fully open.<br />

11. Record the system’s pressure differential at the pressure transmitter with the system<br />

at full flow. Adjust the coil closest to the pump closed <strong>and</strong> verify the pressure transmitter<br />

setting. Continue with the next coil until enough coils are closed to equal the minimum<br />

speed <strong>of</strong> the pump or the minimum flow through the primary heat exchangers. Verify that<br />

the closed valves closest to the pump remain closed <strong>and</strong> are not lifting <strong>of</strong>f their seats.<br />

Note that most bypasses in two-way valve systems act as a relief valve <strong>and</strong> the pump will<br />

ride its pressure curve until bypass opens. Record the minimum flow across the heat<br />

exchanger.<br />

12. Verify the coil or heat exchangers controller calibration, <strong>and</strong> record the entering <strong>and</strong><br />

leaving water temperatures.<br />

80

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!