Condenser<br />
• the design <strong>and</strong> actual temperature<br />
Electrical<br />
• the design <strong>and</strong> actual voltage for the compressor( s)<br />
• the design <strong>and</strong> actual amperage for the compressor( s)<br />
• the design <strong>and</strong> actual voltage for the condenser fan( s)<br />
• the design <strong>and</strong> actual amperage for the condenser fan( s)<br />
<strong>Air</strong> Cooled Chiller With Remote Condenser( s)<br />
The air-cooled chiller with remote condenser(s) consists <strong>of</strong> compressors <strong>and</strong> liquid<br />
coolers or evaporators that connect to one or more air-cooled condensers.<br />
The basic test for the air-cooled chiller with remote condenser is the same as <strong>Air</strong> Cooled<br />
Chillers with the condenser data being not applicable.<br />
<strong>Air</strong> Cooled Condenser<br />
The basic test for the air-cooled condenser is shown on the Associated <strong>Air</strong> Balance<br />
Council’s “<strong>Air</strong> Cooled Condensing Unit” report form. The basic procedure is to measure<br />
<strong>and</strong>/or report the following:<br />
• Condenser manufacturer nameplate data<br />
• Rated capacity in tons<br />
• Model <strong>and</strong> serial number<br />
• The design <strong>and</strong> actual entering air temperature<br />
• The design <strong>and</strong> actual voltage for the condenser fan( s)<br />
• The design <strong>and</strong> actual amperage for the condenser fan( s)<br />
97