17.11.2012 Views

Balancing of a Water and Air System (PDF

Balancing of a Water and Air System (PDF

Balancing of a Water and Air System (PDF

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

26<br />

Verify minimum flow setting.<br />

13. Set terminals to minimum, <strong>and</strong> adjust the inlet vane or speed controller until<br />

minimum static pressure <strong>and</strong> airflow are obtained.<br />

14. Temperature control personnel, balancing personnel, <strong>and</strong> the design engineer should<br />

agree on the final placement <strong>of</strong> the sensor for the static pressure controller. This sensor<br />

must be placed in a representative location in the supply duct to sense average<br />

maximum <strong>and</strong> minimum static pressures in the system.<br />

15. Check return air fan speed or its inlet vane damper, which tracks or adjusts to the<br />

supply fan airflow, to ensure proper outside air volume.<br />

16. Operate the system on 100% outside air (weather permitting), <strong>and</strong> check supply <strong>and</strong><br />

return fans for proper power <strong>and</strong> static pressure.<br />

Fan Tracking<br />

As supply system airflows <strong>and</strong> pressures change, consideration must be given as to how<br />

the return air, outside air <strong>and</strong> relief air track.<br />

Volumetric Tracking<br />

Volumetric tracking is the preferred method <strong>of</strong> measurement. Tracking is accomplished<br />

by measuring the airflows <strong>of</strong> two fan systems. This maintains a difference for constant<br />

minimum outside air volume <strong>and</strong> building pressurization. Fan selection is critical to<br />

prevent surges or unstable operation <strong>of</strong> the controls. Surge can occur as the fan<br />

approaches a point where there is insufficient air entering the fan wheel to completely fill<br />

the space between the blades. Surge will be indicated by a fluctuation in CFM <strong>and</strong> static<br />

pressure, <strong>and</strong> will create a noisy operation.<br />

Sizing <strong>of</strong> the calibrated airflow station is also critical in the air h<strong>and</strong>ling unit operation.<br />

Unstable operation <strong>of</strong> controls occurs when the velocity drops below 600 fpm (3 m/s)<br />

where the air measuring station is out <strong>of</strong> range. Most transducers require at least 0.02”wc<br />

<strong>of</strong> pressure to operate properly. Consideration must also be made on the high end to not<br />

exceed the transducer’s range.<br />

Plenum Pressurization Tracking<br />

Plenum pressurization is the control <strong>of</strong> fan speed <strong>and</strong> minimum outside air<br />

volumes by constant plenum pressure. The control <strong>of</strong> supply fan speed or vane control is<br />

accomplished by maintaining a constant duct pressure at various volumes at a point<br />

designated for control, usually 2/3 distance down the supply duct. The minimum outside<br />

air volume is maintained with a constant mixed air plenum pressure controlling the<br />

return air damper. The purge (exhaust) damper is controlled by building pressure. The<br />

return fan speed is controlled by a constant return fan discharge plenum pressure. The<br />

26

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!