46<br />

Table 11 D<br />

Enthalpy at saturation, Btu per pound <strong>of</strong> dry air at 29.92”<br />

Dry Bulb on left, Wet Bulb on top<br />

58 57 56 55 54 53 52 51 50 49 48 47 46 45<br />

68 25.06 24.41 23.78 23.15 22.54 21.94 21.36 20.78 20.21 19.66 19.12 18.61 18.09 17.58<br />

66 25.07 24.42 23.79 23.16 22.55 21.95 21.37 20.79 20.22 19.67 19.13 18.62 18.10 17.59<br />

64 25.09 24.44 23.80 23.17 22.57 21.96 21.38 20.80 20.23 19.68 19.14 18.63 18.11 17.59<br />

62 25.10 24.45 23.81 23.18 22.58 21.97 21.39 20.81 20.24 19.69 19.15 18.64 18.12 17.60<br />

60 25.11 24.46 23.82 23.19 22.59 21.98 21.40 20.82 20.25 19.70 19.16 18.64 18.13 17.60<br />

58 25.12 24.47 23.83 23.20 22.60 21.99 21.41 20.83 20.26 19.71 19.17 18.65 18.13 17.61<br />

56 23.84 23.21 22.61 22.00 21.42 20.84 20.27 19.72 19.18 18.65 18.14 17.61<br />

54 22.62 22.01 21.43 20.85 20.28 19.73 19.18 18.66 18.14 17.62<br />

52 21.44 20.86 20.29 19.74 19.19 18.66 18.15 17.62<br />

50 20.30 19.75 19.21 18.67 18.15 17.63<br />

48 19.21 18.67 18.16 17.63<br />

46 18.16 17.64<br />

To calculate the total heat removed from air that has gone through an<br />

evaporator<br />

Use a digital sling psychrometer or a sling psychrometer <strong>and</strong>; familiarize yourself with its<br />

operation.<br />

(1) Wet the bulb with distilled water for a sling psychrometer; obtain the wet bulb <strong>and</strong> dry<br />

bulb reading <strong>of</strong> the air going into the fan coil. Leave the psychrometer in the air until the<br />

wet bulb stops moving (this may take 5 minutes or more).<br />

Wet bulb temperature_____________°F<br />

Dry bulb temperature _____________°F<br />

(2) Using a digital sling psychrometer or the sling psychrometer obtain the wet<br />

bulb <strong>and</strong> dry bulb reading <strong>of</strong> the air coming out <strong>of</strong> the fan coil. Leave the psychrometer in<br />

the air until the wet bulb stops moving (this may take 5 minutes).<br />