54<br />

<strong>System</strong> balance becomes more important in terminals with a large temperature difference.<br />

Less water flow is required, which reduces the size <strong>of</strong> pipes, valves, <strong>and</strong> pumps, as well as<br />

pumping costs. A more linear emission curve gives better system control. If flow varies by<br />

more than 5% at design flow conditions, heat transfer can fall <strong>of</strong>f rapidly, ultimately causing<br />

poorer control <strong>of</strong> the wet-bulb temperature <strong>and</strong> potentially decreasing system air quality.<br />

Heat Transfer at Excessive Flow<br />

Increasing the flow rate above design in an effort to increase heat transfer requires careful<br />

consideration. Figure 3 shows that increasing the flow to 200% <strong>of</strong> design only increases heat<br />

transfer by 6% but increases resistance or pressure drop four times <strong>and</strong> power by the cube <strong>of</strong><br />

the original power (pump laws) for a lower design ∆t. In coils with larger waterside design ∆t,<br />

heat transfer can increase.<br />

Hydronic Pressure Measuring Instruments<br />

Manometer U-tube<br />

The U-tube manometer has primarily been used for measuring pressure drops across terminal<br />

heat exchangers <strong>and</strong> flow meters. There is no calibration required <strong>and</strong> other instruments can<br />

be verified against the manometer.<br />

Digital Manometer for <strong>Water</strong> Measurement<br />

There are several manufacturers <strong>of</strong> digital manometers <strong>and</strong> each has specific functions it can<br />

perform. The st<strong>and</strong>ard requirements <strong>of</strong> the digital manometer is it can read in English units or<br />

metric, has a broad range <strong>of</strong> pressures, can display in pounds per square inch (psi), foot head<br />

(R), inches <strong>of</strong> water column (in. wc), <strong>and</strong> kilo Pascal’s (kPa). Each manometer should have<br />

auto zeroing capabilities.<br />

The manufacturer’s pressure rating <strong>and</strong> calibration instructions should be followed. When<br />

used to measure pressures, the calibration shall be verified by using a U-tube manometer or a<br />

calibrated pressure gauge. The calibration verification can also be accomplished by using a<br />

dead weight kit.<br />

The accuracy <strong>of</strong> the gauge reading on differential pressure shall be ±2% <strong>of</strong> reading ±1<br />