S-Y(St)Y...Screened signal cableStandard: VDE 0813CONSTRUCTIONConductor: soft annealed copper wire of 0.6 mm diameter.Insulation: PVC compound.Twisting elements: pairs, triples.Cable core: group stranded.Core wrapping: thermoplastic tape.Screen: laminated aluminium foil with a copper drain wirelongitudinally applied under it.Sheath: PVC compound.Sheath colour grey.APPLICATIONIt can use for transmission of low-frequency commands insignalling equipment.ELECTRICAL CHARACTERISTICSCharacteristicUnitValue for0,6 mmLoop resistance, max Ω/km 130Insulation resistance, min20 °C50 °CMΩ km 1001Mutual capacitance, max nF/km 120Capacitance unbalance, maxkepF/100m 50150*Dielectric strength800Veffwire/wire800Operating voltage, max Veff 200Loss meter tangent 0.1* Permissible exceeding for 10 % of value, and min. One is 300 pF/100 m118CONSTRUCTION DATAConstructionFor conductor 0,6 mmCu number Diameter Mass[kg/km] [mm] [kg/km]1x2x0,6 6 4.5 253x2x0,6 17 5.5 404x2x0,6 23 6.0 505x2x0,6 29 6.5 606x2x0,6 35 7.0 6510x2x0,6 58 8.5 10011x2x0,6 63 8.7 10512x2x0,6 69 9.0 11015x2x0,6 86 9.8 14016x2x0,6 92 10.0 1455x3x0.6 41 7.5 8010x3x0.6 82 10.0 14011x3x0.6 90 10.5 15015x3x0.6 122 11.5 19518x3x0.6 147 12.5 23520x3x0.6 163 13.0 26021x3x0.6 171 13.5 27024x3x0.6 196 14.0 30525x3x0.6 204 14.5 31528x3x0.6 228 15.0 350