12.07.2015 Views

CABLES AND WIRES - Novkabel

CABLES AND WIRES - Novkabel

CABLES AND WIRES - Novkabel

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Table: Correction factor for cables coiled on a reelNo. Of layerson a reelCorrectionfactor1 2 3 4 50,80 0,61 0,49 0,42 0,38Current load of PVC and XLPE insulated cables for nominalvoltage 0,6/1 kVTable: Cables with PVC insulation, laid in the airPermitted operatingtemperatureAir temperatureInsulation70 O C30 O CPVCConductor Copper AluminiumMethod of cableinstallationMulti-coreSingle-core - intriangleIn airMulti-coreSingle-core - intriangleNo. of loaded cores 3 3 3 3Nominal cross-sectionof Cu conductors(mm 2 )Load(A)1,5 19,5 21 - -2,5 25 28 - -4 34 37 - -6 43 47 - -22210 59 64 - -16 79 84 - -25 106 114 82 8735 129 139 100 10750 157 169 119 13170 199 213 152 16695 246 264 186 205120 285 307 216 239150 326 352 246 273185 374 406 285 317240 445 483 338 378300 511 557 400 437400 597 646 472 513500 669 747 539 600