12.07.2015 Views

CABLES AND WIRES - Novkabel

CABLES AND WIRES - Novkabel

CABLES AND WIRES - Novkabel

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

PP/RInstallation cable with PVCStandard: SRPS N.C3.230Nominal voltage: 380 VTest voltage: 2 kVCONSTRUCTIONConductor: annealed copper wire class 1, according to SRPSN.C0.015.Insulation: PVC compound.Sheath: PVC compound layer over 2 or 3 cores, which are laidparallel. The layer is forming the track between the cores, withthe notch in the middle of the track, this making possibletemporary fixing of the cables.Sheath colour can be grey or black.APPLICATIONIn dry conditions indoors, for laying in plaster or under plaster,without special mechanical protection. Suitable for installations inobjects made of prestressed concrete, vibrated concrete orprefabricated elements, when the notches for laying the roundcables can not be made. Not for use in wooden object, nor in openair.CONSTRUCTION DATAn x qCu number Height x width Mass[mm 2 ] [kg/km] [mm] [kg/km]2x1,5 29 4,4x12,0 662x2,5 48 5,2x13,5 983x1,5 43 4,4x19,5 1043x2,5 72 5,2x22,5 151037n – number of the wire, q – nominal cross section of the conductorPermissible conductor temperature:- operating temperature, max +70°C,- in short circuit (max 5 s), max +160°C.Permissible environment temperature:- at laying and handling, min +5°C.Smallest bending radius: 4a (a – cable height).

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!