PP/JZFlexible cable with electrical protectionStandard: PSNNominal voltage U 0 /U: 300/500 VTest voltage:2 kVCONSTRUCTIONConductor: flexible copper strand class 5, according to SRPSN.C0.015.Insulation: PVC compound.Core: 2 to 5 cores are stranded together.Filling: suitable material.Electric protection: braid of bare or tinned copper wires.Sheath: PVC compound.Sheath colour can be white, grey or black.APPLICATIONFor connection of mobile user devices at medium mechanicaltensile strains, where one cannot expect mechanical damages andelectric shock risk, near data processing and data transfer devicesand cables.CONSTRUCTION DATAn x q Cu number Diameter Mass n x q Cu number Diameter Mass[mm 2 ] [kg/km] [mm] [kg/km] [mm 2 ] [kg/km] [mm] [kg/km]2x0,75 15 8,7 105 4x0,75 29 10,2 1432x1,0 19 9,5 120 4x1,0 38 11,0 1702x1,5 29 9,8 133 4x1,5 58 11,7 2052x2,5 48 12,4 210 4x2,5 96 14,0 3053x0,75 22 9,3 120 5x0,75 36 11,0 1703x1,0 29 10,0 140 5x1,0 48 11,8 2003x1,5 43 11,0 175 5x1,5 72 11,9 2353x2,5 72 13,1 250 5x2,5 120 15,2 355043n – number of the wire, q – nominal cross section of the conductorPermissible conductor temperature:- operating temperature, max +70°C,- in short circuit (max 5 s), max +160°C.Permissible environment temperature:- at laying and handling, min +5°C.Smallest bending radius: 5D (D – cable diameter).