12.07.2015 Views

CABLES AND WIRES - Novkabel

CABLES AND WIRES - Novkabel

CABLES AND WIRES - Novkabel

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

H05RN-FFlexible rubber cableStandard: DIN VDE 0282-4, HD 22.4Nominal voltage U 0 /U: 300/500 VTest voltage:2 kVCONSTRUCTIONConductor: copper conductor class 5.Insulation: based on EPR rubber (EI4).Sheath: based on polychloroprene rubber (EM2),oil resistant, flame retardant.APPLICATIONCable can be used in dry locations such as homes and offices forsupplying portable or light mobile appliances with low mechanicalstresses. One-wire cable can be used for a range of bulbs for theNew Year's tree and a similar purpose.CONSTRUCTION DATAnxq Cu number Diameter Mass[mm 2 ] [kg/km] [mm] [kg/km]1x0,75 8 4,4 271x1 10 4,5 301x1,5 15 4,8 362x0,75 15 6,8 602x1 20 7,3 710613G0,75 22 7,4 743G1 29 7,7 84n – number of the cores; q – nominal cross section conductorPermissible conductor temperature:- operating temperature, max +60°C,- in short circuit (max 5 s), max +200°C.Permissible environment temperature:- mobile from -25°C to +40°C,- fixed laying from -30°C to +40°C.Smallest bending radius: 3D (D - cable diameter).