H05ZHalogen free cablesStandard: DIN VDE 0282-9; HD 22.9Nominal voltage U 0 /U: 300/500 VTest voltage:2000 VH05Z-KH05Z-UCONSTRUCTIONConductor: in accordance with DIN VDE 0295 fortype:H05Z-U copper conductor, class 1H05Z-K copper conductor, class 5Insulation: slow-burning material - based on thepolyolefin or the suitable synthetic polymer(EI5, DIN VDE 0282-1)APPLICATIONInsulated conductor can be used for installation, in the dry room,lighting equipment and control instruments.Cable H05Z has the same application as H05V cable, but it ishalogen free.CONSTRUCTION DATAq Cu Number Diameter Mass[mm 2 ] [kg/km] [mm] [kg/km]0,5 4,9 2,3 9,60,75 7,4 2,5 12,41 9,8 2,7 15,0q – nominal cross section of the conductorPermissible conductor temperature:- operating temperature, max +90°C- in short circuit (max 5 s), max +250°CPermissible envirement temperature:- at laying and handling, min +5°C- at storage, max +40°CSmallest bending radius: 4D (D – cable diameter)145