12.07.2015 Views

CABLES AND WIRES - Novkabel

CABLES AND WIRES - Novkabel

CABLES AND WIRES - Novkabel

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

H05RR-FПРСFlexible cable with rubber insulation and sheathStandard: DIN VDE 0282-4, HD 22.4Nominal voltage U 0 /U: 300/500 VTest voltage:2 kVCONSTRUCTIONConductor: copper conductor class 5.Insulation: based on EPR rubber (EI4).Sheath: based on EPR rubber (EM3).Sheath colour black.APPLICATIONCable can use in dry locations such as homes and offices forsupplying portable or light mobile appliances with low mechanicalstresses (e.g. vacuum cleaners, electric irons, cooking appliances).It can not be used for fixed laying in open air.CONSTRUCTION DATAnxq Cu number Diameter Mass nxq Cu number Diameter Mass060[mm 2 ] [kg/km] [mm] [kg/km] [mm 2 ] [kg/km] [mm] [kg/km]2x0,75 15 6,8 55 4G0,75 29 8,0 782x1 20 7,3 65 4G1 39 8,5 952x1,5 29 8,8 97 4G1,5 58 10,5 1442x2,5 48 10,3 137 4G2,5 96 12,0 2103G0,75 22 7,4 69 4G4 154 14,5 3143G1 29 7,7 79 4G6 231 16,6 4323G1,5 44 9,3 116 5G0,75 36 9,0 1043G2,5 72 11,0 168 5G1 48 9,3 1193G4 116 13,0 247 5G1,5 72 11,5 1773G6 173 15,0 341 5G2,5 120 13,5 268n – number of the cores; q – nominal cross section conductorPermissible conductor temperature:- operating temperature, max +90°C,- in short circuit (max 5 s), max +250°C.Permissible environment temperature:- at laying and handling, min -25°C,- for storage from +10°C to +40°C.Smallest bending radius: 3D (D - cable diameter).